English
Language : 

DRAN60-12A Datasheet, PDF (1/4 Pages) Chinfa Electronics Ind. Co., Ltd. – AC - DC DIN RAIL MOUNTABLE 60W INDUSTRIAL CONTROL EQUIPMENT
DRAN60 SERIES
FOR DC BACKUP SYSTEM
AC - DC DIN RAIL MOUNTABLE
60W
INDUSTRIAL CONTROL EQUIPMENT
FEATURES
COMPACT DESIGN
SIMPLE IN APPLICATION
LOW PRICING
WORKABLE FOR BOTH POWER SUPPLY / DC
BACKUP SYSTEM
SELECTION CHART
DRAN 60 - 24 A *
Wattage
12 : 13.6V OUT
24 : 27.2V OUT
48 : 54.5V OUT
DC Backup System
SCREW TERMINALS
MODEL LIST
INPUT
MODEL NO.
VOLTAGE
DRAN60-12A*
DRAN60-24A*
DRAN60-48A*
85~264 VAC
85~264 VAC
85~264 VAC
OUTPUT OUTPUT
WATTAGE VOLTAGE
Single Output Models
60 WATTS
60 WATTS
60 WATTS
+ 13.6 VDC
+ 27.2 VDC
+ 54.5 VDC
OUTPUT
CURRENT
4.4 A
2.2 A
1.1 A
EFF.
(min.)
84%
86%
86%
EFF.
(typ.)
86%
89%
89%
- - ++Rdy
DRAN60
Series
+
Rdy
D1
-
-
K1
Fuse
K1
BATTERY
LOAD
DRAN60 Series For DC Backup System Application
Note
1.The suffix "*" is part of the model number, which specifies the product is designed and pre-trim for low-cost DC backup power system with
external Lead-Acid battery, Relay and Fuse.
2.The manufacturer is liable neither for the external components nor the damage to the power supply causing by external components.
3.The total consumption current including loading and battery charging current should not exceed the maximum rated current of power supply.
4.The operation concept of DC backup power system
A. When AC power alive The "Rdy" is close circuit to active the external Relay . The power supply feeds current into the external loads and
charges through Relay to the external battery as well.
B. When AC power interrupted The "Rdy" is remain close circuit to maintain the external Relay remain active, the external battery supply
current to the external loads.
C. When Battery power low The "Rdy" become open circuit and the external Relay become inactive to disconnect the battery from
external loads.
www.chinfa.com
2008.03.28
sales@chinfa.com