English
Language : 

SVTA4684 Datasheet, PDF (4/6 Pages) celduc-relais – DIGITAL THREE PHASE ANGLE CONTROLLER
celduc ®
relais
S/GRA/SVTA4684/A/03/07/2002
Page 4/6 GB
INTERNAL POWER SUPPLY
CHARACTERISTIC
Terminals
Mains voltage range
Consumption
Mains frequency range
Turn-on time
LABEL
Ue
Is
F
tm
VALUE
3L2 & 5L3
200->480VAC
1mA typical
40-65Hz
100ms
INFO.
GENERAL INFORMATION
Connections
Screwdriver advised
Min and max tightening torque
Number and cross section of the
wires
Screwdriver for settings
Housing
Mounting
Noise level
Weight
Power
Input terminal block
Posidriv 2 or 0.8 x 5.5mm
0.8 x 2mm
1.8->3N.m
2 x 1.5->6mm2
(10mm2 without ferrule)
0.8 x 2mm
1 x 2.5mm2
UL94V0
Omega DIN rail (DIN50022) or screwed
Low audible vibrations
500g
STANDARDS
Standards
Protection level
Protection against direct touch
CE marking
UL, cULUS and VDE approvals
EN60947-4-2 & EN60947-4-3
IP2L0
Accordin to V.D.E. 160 part 100 :
Back hand and finger safety
Yes
Pending
TYPE OF TEST
STANDARD
E.S.D. (Electrostatic discharges) EN61000-4-2
Radiated electromagnetic fields EN61000-4-3
Fast transients bursts
EN61000-4-4
Electric chocks
Voltage drop
EN61000-4-5
EN61000-4-11
LEVEL
8kV (air)
4kV (touch)
10V/m
2kV direct coupling on the power side
2kV coupling by clamp on the input side
1kV direct coupling differential mode (input and output)
2kV direct coupling common mode (input and output)
-
EFFECT
No effect
No effect
No effect
No effect
Radiated and conducted
disturbances
NFEN55011
The conducted or radiated disturbances generated by
solid state relays depend on the wiring and load
configuration.
The test method recommended by the European standards
and concerning electromagnetic compatibility leading to
results far from reality, we decided to advise our customer
in order to adapt their filtering scheme to their application.
Please refer to the SVTA – SWTA installation
manual.