English
Language : 

SIB765170 Datasheet, PDF (2/4 Pages) celduc-relais – AC Semiconductor Contactor
celpac®
S/CLP/SIB765170/B/21/04/2004
page 2 / 4GB
Control characteristics (at 25°C)
for each input :
Two inputs can be mounted in parallel or in serie
DC
Input : Ic = f( Uc)
Paramètre / Parameter
Symbol Min Nom Max Unit 12
Control voltage
Uc
3,5 5-12-24 32 V
10
Control current (@ Uc )
Release voltage
Input LED
Reverse voltage
Ic
<10 <10 <10 mA
8
Uc off 2
green
V
6
Urv
32
V
4
Clamping voltage
Uclamp
42
V
2
Input immunity : EN61000-4-4
Input immunity : EN61000-4-5
2kV
2KV
0
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
Uc ( VDC)
Output characteristics (at 20°C)
Parameter for each way
Conditions
Symbol
Typ.
Unit
Load voltage
Ue
400
V rms
Operating range
Uemin-max
24-510
V rms
Peak voltage
Up
1200
V
Clamping voltage
Uclamp 820 (@1mA)
V
Zero cross level
Usync
random
V
Latching voltage
Ie nom
Ua
8
V
AC-51 nominal current : permanent
( see Fig. 2 page 3) Ie AC-51
2 x 22
A rms
AC-53 nominal current
Ie AC-53
2 x 12
A rms
Non repetitive overload current
tp=10ms (Fig. 3)
Itsm
550
A
On state voltage drop (typical value)
@ 25°C
Vt
0,9
V
Dynamic resistance (typical value)
rt
8
mΩ
Output Power dissipation (typical value) : for each way ( ==> x2)
Pd
0,81xIe+0,08xIe2 W
Thermal resistance between junction to air
Off state leakage current
Minimum load current
Turn on time
Turn off time
Operating frequency range
Off state dv/dt
Maximum di/dt non repetitive
I2t (<10ms)
Conducted immunity level
Conducted immunity level
Short circuit protection
@Ue, 50Hz
Uc nom DC ,f=50Hz
Uc nom DC ,f=50Hz
IEC 1000-4-4 (burst)
IEC 1000-4-5(schocks)
FERRAZ
Rthj/a
2,2 (1,8)
K/W
Ilk
<1
mA
Iemin
5
mA
ton max
0,1
ms
toff max
10
ms
f
0,1-440
Hz
dv/dt
500
V/µs
di/dt
50
A/µs
I2t
1500
A2s
4kV criterion A
4kV criterion A
gRC 25A/32A/50A/63A 14x51
General characteristics (at 20°C)
Input to output insulation
Output to case insulation
Insulation resistance
Rated impulse voltage
Protection level / CEI529
Pollution degree
Vibration resistance 10 -55 Hz according to CEI68 :
Shocks resistance according to CEI68 ( on DIN rail / with screws)
Ambient temperature (with no icing or condensation)
Storage temperature (with no icing or condensation)
Ambient humidity
Weight
Conformity
Conformity
Ui
Ui
Ri
Uimp
-
-
double amplitude
-
-
HR
4000
4000
100 (@500VDC)
4000
IP20
2
1,5
30/50
-30 /+80
-30/+100
40 to 85
450
EN60947-4-3 (IEC947-4-3)
EN60950 UL/cUL pending
VRMS
VRMS
MΩ
V
mm
g
°C
°C
%
g
celduc
relais
www.celduc.com
Rue Ampère B.P. 4
42290 SORBIERS - FRANCE E-Mail : celduc-relais@celduc.com
Fax +33 (0) 4 77 53 85 51
Service Commercial France Tél. : +33 (0) 4 77 53 90 20
Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tél. +33 (0) 4 77 53 90 19