English
Language : 

CA3-B0-10-450-121-C Datasheet, PDF (7/24 Pages) Carling Technologies – Circuit Breaker

C-Series Handle UL Recognized – Ordering Scheme | 7
C
1
Series
A
2
Actuator
3
3
Poles
—B
4
Circuit
0 — 10 — 450 — 1
5
Aux/Alarm
Switch
6
Frequency
& Delay
7
Current Rating
8
Terminal
2
9
Actuator
Color
1 —C
10
Mounting
Bezel/Barrier
11
Agency
Approval
1 SERIES
C
2 ACTUATOR1
A Handle, one per pole
B Handle, one per multipole unit
S Mid-Trip Handle, one per pole
T Mid-Trip, one per pole & Alarm Switch
3 POLES2
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4 CIRCUIT3
A3 Switch Only (no coil)
B Series Trip (current)
C Series Trip (voltage)
D4 Shunt Trip (current)
E4 Shunt Trip (voltage)
F4 Relay Trip (current)
G4 Relay Trip (voltage)
H4,5 Dual Coil with Shunt Trip
Voltage Coil
K4,5 Dual Coil with Relay Trip
Voltage Coil
5 AUXILIARY/ALARM SWITCH
0 without Aux Switch
2 S.P.D.T., 0.110 Q.C. Terminal
3 S.P.D.T., 0.139 Solder Lug
4 S.P.D.T., 0.110 Q.C. Terminal
(Gold Contacts)
6 S.P.S.T., 0.139 Solder Lug
8 S.P.S.T., 0.187 Q.C. Terminal
9 S.P.D.T., 0.187 Q.C. Terminal
7 CURRENT RATING (AMPERES)
CODE AMPERES
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
095 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
VOLTAGE COIL (NORMINAL RATED VOLTAGE)7
CODE RATING
A06 6DC
A12 12DC
A18 18DC
A24 24DC
A32 32DC
A48 48DC
A65 65DC
J06 6AC
J12 12AC
J18 18AC
J24 24AC
J48 48AC
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
6609 60.000
6709 70.000
6809 80.000
6859 85.000
6909 90.000
6959 95.000
8109 100.000
J65 65AC
K20 120AC
L40 240AC
6 FREQUENCY & DELAY
033 DC 50/60Hz, Switch Only
107 DC Instantaneous
11 DC Ultra Short
12 DC Short
14 DC Medium
16 DC Long
207 50/60Hz Instantaneous
21 50/60Hz Ultra Short
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC 50/60Hz Instantaneous
31 DC 50/60Hz Ultra Short
32 DC 50/60Hz Short
34 DC 50/60Hz Medium
36 DC 50/60Hz Long
428 50/60Hz Short, Hi-Inrush
448 50/60Hz Medium, Hi-Inrush
468 50/60Hz Long, Hi-Inrush
528 DC Short, Hi-Inrush
548 DC Medium, Hi-Inrush
56 DC Long, Hi-Inrush
Notes:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
Actuator Code:
A: Handle tie pin spacer(s) and retainers provided assembled with multi-pole units.
B: Handle location as viewed from front of breaker:
2 pole - left pole
3 pole - center pole 4 pole - two handles at center poles
5 pole - three handles at center poles
6 pole - four handles at center poles
S: Handle moves to mid-position only upon electrical trip of the breaker. Available with
circuit codes B, C, D, E, F, G, H and K.
T: Handle moves to mid-position and alarm switch activates only upon electrical trip of
the breaker. Available with circuit codes B & C.
Standard multipole units have all poles identical except when specifying auxilary switch
and/or mixed poles. 4 pole max w/VDE. 5th pole available as Series Trip w/Voltage Coil only.
Switch Only circuits, rated up to 50 amps and 6 poles, and only available with VDE Certi-
fication when tied to a protected pole (Circuit Code B, C, D or H.). For .02 to 30 amps,
select Current Code 630. For 35 - 50 amps, select Current Code 650. For 55-70 amps,
select Current Code 670. For 75-100 amps, select Current Code 810.
Circuit Codes D,E,F,G,H & K available with Terminal Codes 1,2,4 & 5 only. Circuit Codes
D, F, H & K available up to 50 amps maximum Current Rating.
Consult factory for available Dual Coil options, as special catalog number is required.
Dual Coil Voltage Coils with Shunt Trip Construction trip instantaneously on line voltage.
Dual Coil Voltage Coils require 30VA minimum power to trip instantaneously and are
rated for intermittent duty only.
ers, one aux. switch is supplied, mounted in the extreme right pole.
Voltage coils not rated for continuous duty. Available only with delay codes 10 and 20.
Available with Circuit Codes B & D only, and up to 50 amps maximum.
Current Ratings 60 - 70 are available up to four poles maximum. Ratings 71 - 100 are
available up to two poles maximum.
Terminal Code 1 available to 60 amps maximum.
Terminal Codes 2,4,5 and C available to 50 amps maximum.
Terminal Codes 3,6 & 9 available to 100 amps maximum.
Terminal Code 7 available to 25 amps maximum.
Terminal Code A available to 100 amps maximum.
Terminal Codes 7,8,9 & C are not VDE approved.
No marking available. Consult factory. VDE/TUV Approval requires dual (I-O, ON-OFF)
or I-O markings on all handles.
Single pole only.
VDE/TUV: 30 amps max.; UL/CSA: 50 amps max.; Available in 2 - 4 poles only and
limited to AC Delays. “General Purpose amps” not rated for “full load amps” or to be
used in applications with a motor.
8 TERMINAL15
110 Stud 10-32, threaded
211 Screw 10-32
312 Screw 1/4-20, threaded
411 Screw M5 x 0.8, threaded
511 Screw M5 x 0.8
612
713,15
815
912,15
A14
C11,15
Screw M6, threaded
0.250 Double Click Connect
1/4” Clip Terminal
7/16” Clip Terminal
Plug-In Stud
5/16” Clip Terminal
9 ACTUATOR COLOR & LEGEND16
Actuator Color
I-O
ON-OFF
White
A
B
Black
C
D
Red
F
G
Green
H
J
Blue
K
L
Yellow
M
N
Gray
P
Q
Orange
R
S
Black (short handle)17 T
U
Dual
1
2
3
4
5
6
7
8
9
Legend Color
Black
White
White
White
White
Black
Black
Black
White
10 MOUNTING/BARRIERS
MOUNTING STYLE
BARRIERS
VOLTAGE
Threaded Insert
1 6-32 x 0.195 inches
no
< 300
A 6-32 x 0.195 inches
yes
< 300
C18 6-32 x 0.195 inches
yes
2 ISO M3 x 5mm
no
<>–
300
300
B ISO M3 x 5mm
yes
< 300
D18 ISO M3 x 5mm
yes
>– 300
Front Panel Snap-In, 1.00” [25.4mm] wide bezel
E17 with Handleguard
no
< 300
11 AGENCY APPROVAL
C UL Recognized, CSA Accepted
D VDE Certified, UL Recognized, CSA Accepted
E TUV Certified, UL Recognized, CSA Accepted
H UL489 Construction: VDE Certified, UL Recognized, CSA Accepted
I UL Rec. STD 1077, UL Rec. 1500 (ignition protected), CSA Accepted
L UL489 Construction: UL Recognized, CSA Accepted
R UL489 Construction: TUV Certified, UL Recognized, CSA Accepted
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231