N11-B0-24-610-121 Datasheet, PDF (3/10 Pages) Carling Technologies – CIRCUIT BREAKER
N-Series Circuit Breaker - General Specifications | 3
Electrical
Current Metering
I~
(FROM 1 - 30 AMPS)
Integrated current transformer.
Measurement range: 1-30 Amps.
Voltage output: 10mV per Amp
according to the formula below:
2(Amp) ≤ I ≤ 30(Amp)
V = 0.01× I ± 2%
(with current metering codes 1 or 2)
V = 0.01× I ±1%
(with current metering codes 3 or 4)
V V10
I I10
V10
I10
0.85%
Where V=CT output in volts
V10=CT output in volts with
I=I10=10 (A); I=primary current in
amperage (50/60 Hz). Phase shift
between primary current and CT
output is 0.25±0.25°. Maximum
crest factor of primary current is 1.73.
R1 shall be integrated in the breaker.
R2 and R3 are provided by end user
and external to the breaker.
Connection: below Load Terminal.
2-pin connector, Molex 35362-0250.
Mating Connector housing – Molex
PN35507-0200.
(Current metering is available on AC
rated devices only)
R1=28Ω±Y%
R2=14Ω±Y%
V
R3=14Ω±Y%
I : 1400 CT
V=0.01 X (I)
Note: When current metering code is 1 or 2; Y to equal 1.0
When current metering code is 3 or 4; Y to equal 0.1
Dielectric Strength
Impedance
Insulation Resistance
Overload
Interrupt Capacity
UL, CSA-1960V 50/60 Hz for one
minute between all electrically
isolated terminals. Comply
with the 8mm spacing and 3750V
50/60 Hz dielectric requirements
from hazardous voltage to operator
accessible surfaces and between
main circuits of adjacent poles per
Publications EN 60950 and VDE 0805
See next page
Minimum of 100 Megohms @ 500VDC
50 operations @ 600% of rated current
for AC rated devices
See table A
Mechanical
Endurance
Trip Free
Trip Indication
10,000 “On-Off” operations @ 6 per
minute; with rated current & voltage
Trips on overload even when
actuator is forcibly held in the “On”
position
The operating actuator moves
positively to the “Off” position
when an overload causes the
breaker to trip
Environmental
Environmental
Operating Temperature
Vibration
Shock
Thermal Shock
Moisture Resistance
Salt Spray
MIL-PRF-55629 and MIL-STD-202G
-40°C to +85°C
Withstands 0.06” excursion
from 10-55 Hz and 10Gs 55-500 Hz
at rated current per MIL-PRF-55629
and MIL-STD-202G, Method 204D,
Test Condition A. Instantaneous and
ultra-short curves tested at 90% of
rated current
Withstands 50 Gs, 6 ms saw tooth
while carrying rated current per
MIL-PRF-55629 and MIL-STD-202G,
Method 213B, test condition “I”.
Instantaneous and ultra short curves
tested at 90% of rated current
MIL-PRF-55629 and MIL-STD-202G,
Method 107G, Condition A (5-cycles
at -55ºC to +25ºC to +85ºC to +25ºC)
MIL-PRF-55629 and MIL-STD-202G,
Method 106G, i.e., Ten 24-hour
cycles at +25°C to +65°C, 80-98% RH
Method 101, Condition A (90-95%
RH @ 5% NaCl Solution, 96hrs)
Physical
Number of Poles
1 - 2 poles
Termination
Wire ready and touch proof wire
clamp (See Figure 1). Accepts up
to (2) #10 AWG wires per terminal.
Designed for use with solid,
stranded and flexible stranded
wires, with or without ferrule or pin
terminals. Also accepts straight fork
and flanged fork terminals.
Termination Torque
15-20 in-lbs (Line & Load terminals)
Termination Barrier
Integral sliding barrier to comply
with spacing requirements
(See figure 1)
Mounting
Threaded Insert: #6-32 UNC-2B, or
M3X0.5-6H B ISO
Insert Termination Torque 7-9 in-lbs
Actuator
Rocker, with or without guard
(See figures 1, 2, and 4)
Internal Circuit Config. Series Trip
Materials
Housing - Glass Filled Polyester
Rocker – Nylon
Line/Load Terminals - Copper Alloy;
Bright Acid Tin Plated
Weight
~107 grams (~3.76 ounces) per pole
Standard Color
Housing – Black
Rocker - Several
(See ordering scheme for colors)
Agency Approvals
UL489, cUL, TUV EN60947-2
Email: sales@carlingtech.com Application Support: team2@carlingtech.com
Phone: (860) 793–9281 Fax: (860) 793–9231 www.carlingtech.com