English
Language : 

L11-B0-24-620-421-DG Datasheet, PDF (3/8 Pages) Carling Technologies – Circuit Breaker

L-Series Circuit Breaker - General Specifications | 3
Electrical
Voltage and Current Ratings
Time Delay
Dielectric Strength
Impedance
UL, CSA-1960V 50/60 Hz for one
minute between all electrically isolated
terminals. Comply with the 8mm
spacing and 3750V 50/60 Hz dielectric
requirements from hazardous voltage
to operator accessible surfaces and
between main circuits of adjacent
poles and from main circuit to auxiliary
circuits per Publications EN 60950 and
VDE 0805.
Insulation Resistance
Overload
Interrupt Capacity
Mechanical
Endurance
Trip Free
Trip Indication
Minimum of 100 Megohms@500VDC
50 operations @ 600% of rated current
5000 AMPs
10,000 “On-Off” Operations @ 6 per
minute; 6000 cycles with rated Current
and Voltage; 4000 cycles without
electrical load.
Trips on overload even when actuator
is forcibly held in the “On” position.
The operating actuator moves
positively to the “Off” position when an
overload causes the breaker to trip.
Environmental
Environmental
MIL-PRF-55629 and MIL-STD-202G
Operating Temperature -40ºC to +85 ºC
Vibration
Withstands 0.06” excursion from 10-55
Hz and 10Gs 55-500 Hz at rated current
per MIL-PRF-55629 and MIL-STD-
202G, Method 204D, Test Condition A.
Instantaneous and ultra-short curves
tested at 90% of rated current.
Shock
Withstands 100 Gs, 6 ms saw tooth
while carrying rated current per MIL-
PRF-55629 and MIL-STD-202G, Method
213B, Test Condition “I”. Instantaneous
and ultra short curves tested at 90% of
rated current.
Thermal Shock
MIL-PRF-55629 and MIL-STD-202G,
Method 107G, Condition A (5-cycles at
-55ºC to +25ºC to +85ºC to +25ºC).
Moisture Resistance MIL-PRF-55629 and MIL-STD-202G,
Method 106G, i.e., Ten 24-hour cycles at
+25ºC to +65ºC, 80-98% RH.
Salt Spray
Method 101, Condition A (90-95% RH @
5% NaCl Solution, 96hrs)
Physical
Number of Poles
Termination
Termination Barrier
Mounting
Actuator
Internal Circuit Config.
Materials
Weight
Standard Color
1-3 poles
Screw Terminals with the following
thread sizes: 10-32, 8-32, M5, M4
Standard for 2 & 3 poles constructions.
Threaded Insert: #6-32 UNC-2B, or
M3X0.5-6H B ISO (2 per Pole)
Rocker, with or without guard.
Series Trip
Housing - Glass Filled Polyester
Rocker – Nylon 6/6
~107 Grams (~3.76 Ounces) per pole.
Housing - Black, Rocker - Black
Regulatory Compliance
Agency Approvals
UL 489, cUL, TUV (EN60934-2)
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231