English
Language : 

RB-11-10-BU1-C Datasheet, PDF (1/3 Pages) Carling Technologies – C-Series Remote Operated Module
Circuit Breaker Accessories
C-Series Remote Operated Module
The Carling Technologies Remote Operated Circuit Breaker
(ROCB) combines the convenience of remote ON, OFF and
Reset capabilities, with the safety and accuracy of a standard
magnetic current sensing device, thus allowing operation of the
breaker from various locations in a system, facility or site (while
not sacrificing the ability to manually operate the breaker if
required). With the ROCB, service, diagnostics, load shedding
and power distribution control functions can now be performed
in areas that were previously unattended, inaccessible or
unsafe.
The ROCB module allows remote operation of the C-Series
panel mount breaker, or the D-Series DIN rail mount breaker
(up to 3 poles) through hard wiring with a single pole, double
throw switch connected to a standard power source, or more
sophisticated relay and modem networks.
The ROCB module can be mounted to either side of the host
breaker, while occupying only the width of a standard C-Series
pole. Several interface methods are available. Remote physical
actuation of the host circuit breaker is achieved by connecting
the ROCB module’s handle with the breakers.
Being based on the C-Series breaker, the ROCB allows easy
adaptation into existing panel designs. In addition, its compact
size allows efficient use of space for new design applications.
With the ROCB, Carling has designed a versatile, compact and
reliable solution -- in a hydraulic/magnetic circuit breaker or
switch only device that can be operated both manually and
remotely.
Design Features include:
• ON-OFF and trip indication
• Load shedding
• Energy management
• Compact size
• Automatic reset capable
• Choice of interface styles
• Panel or DIN rail mounting
• Manual Operation Override
• Fits into industry standard cut-out
ROCB Motor Specifications:
• Voltage input: 12 VDC to 80 VDC
• Start current: < 1 amp
• Switching time: < 2 seconds
To order a remote operated circuit breaker, add / plus the remote module part number to the end of the C-Series
circuit breaker catalog number. ex.CA1BO24620121C/RB1110BU1C
Match color & mounting inserts of breaker.
/ RB
1
Series
1 1 10
2
Mounting
Position
3
Interface
4
Lead Length
B
5
Voltage
Rating
U
6
Actuator
Color
1
7
Mounting
Insert
C
8
Agency
Approval
1 SERIES
RB
2 MOUNTING POSITION
As viewed from back of breaker, line side up, pole 1 left.
0 n/a - ordered separate from breaker
1 Left Side
2 Right Side
3 INTERFACE
1 Flying Leads
2 Integral Connector
3 Flying Leads w/ 4 pin dual row connector (female)
4 Flying Leads w/ 4 pin dual row connector (male)
4 LEAD LENGTH
00 No Lead
01 1”
02 2”
03 3”
04 4”
05 5”
06 6”
07 7”
08 8”
09 9”
10 10”
11 11”
12 12”
13 13”
14 14”
15 15”
16 16”
17 17”
18 18”
19 19”
20 20”
21 21”
22 22”
23 23”
24 24”
25 25”
26 26”
27 27”
28 28”
29 29”
30 30”
5 VOLTAGE RATING
A 12 VDC
B 20-40 VDC
C 41-80 VDC
6 ACTUATOR COLOR
T
White
U
Black
V
Red
W
Yellow
7 MOUNTING INSERT
1 6-32 x 0.195”
2 ISO M3 x 5mm
8 AGENCY APPROVAL
C UL Recognized & CSA Accepted
E TUV Certified, UL Recognized & CSA Accepted
G UL 489 Listed & CSA Certified
I UL 1500 Ignition Protected,UL Recognized & CSA Accepted
J UL 489 Listed, CSA Certified & TUV Certified
Notes:
Available with integral connector only.
Integral and 4-pin dual row connectors not available with agency approval G: UL 489.
120
www.carlingtech.com