English
Language : 

PET2000-12-074NA Datasheet, PDF (6/32 Pages) Bel Fuse Inc. – Full digital controls for improved performance
PET2000-12-074NA
General Condition: TA = 0…55°C, Vi = 230VAC unless otherwise noted.
PARAMETER
V1 nom Nominal Output Voltage
V1 set Output Setpoint Accuracy
dV1 tot Total Static Regulation
P1 nom Nominal Output Power5
P1 peak Peak Output Power6
I1 nom
I1 nom red
I1 peak
I1 peak red
Output Current
Peak Output Current6
V1 pp Output Ripple Voltage7
dV1 load
dV1 line
dV1 temp
dI1 share
VISHARE
dV1 lt
Load Regulation
Line Regulation
Thermal Drift
Current Sharing
Current Share Bus Voltage
Load Transient Response
DESCRIPTION / CONDITION
0.5 ∙ I1 nom, TA = 25°C
Vi min LL to Vi max HL, 0 to 100% I1 nom
Vi min HL to Vi max HL
Vi min LL to Vi max LL
Vi min HL to Vi max HL
Vi min LL to Vi max LL
Vi min HL to Vi max HL
Vi min LL to Vi max LL
Vi min HL to Vi max HL
Vi min LL to Vi max LL
Vi min LL to Vi max HL, 0 to 75% I1 nom, Cext = 0mF
Vi min LL to Vi max HL, 75 to 100% I1 nom, Cext = 0mF
Vi min LL to Vi max HL, 0 to 100% I1 nom, Cext ≥ 1mF/Low
ESR
0 to 100% I1 nom
Vi min HL to Vi max HL, 0.5 ∙ I1 nom
0.5 ∙ I1 nom, TA = 0 ... 55°C
Difference between individual I1,
0 … 8 power supplies in parallel
I1 peak
ΔI1 = 50% I1 nom, I1 = 5 … 100% I1 nom, Cext = 0mF,
ΔI1 = 10% I1 nom, I1 = 0 … 10% I1 nom, Cext = 0mF,
trec
V1 dyn
tV1 rise
tV1 ovr sh
dV1 sense
CV1 load
Recovery Time
Dynamic Load Regulation
Output Voltage Rise Time
Output Turn-on Overshoot
Remote Sense
Capacitive Loading
dI1/dt = 1A/μs, recovery within 1% of V1 nom
ΔI1 = 60% I1 nom, I1 = 1 … 167A, f = 50 ... 5000Hz,
Duty cycle = 10 ... 90%, Cext = 2 ... 30mF
V1 = 10…90% V1 nom, Cext < 10mF
0 to 100% I1 nom
Compensation for cable drop, 0 to 100% I1 nom
MIN
-0.5
-1
0
0
0
0
-83
-24
-8
11.4
6
0
NOM
12.0
2000
1000
2100
1320
-110
0
-0.4
9.14
0.35
0.35
0.5
8
MAX
+0.5
+1
167
83
175
110
120
150
120
-138
24
+8
0.6
0.6
1
12.6
10
0.6
0.25
30
UNIT
VDC
%V1 nom
%V1 nom
W
W
W
W
ADC
ADC
ADC
ADC
mVpp
mVpp
mVpp
mV
mV
mV/°C
ADC
VDC
VDC
VDC
ms
V
ms
V
V
mF
5 See also chapter TEMPERATURE AND FAN CONTROL
6 Peak combined power for all outputs must not exceed 2100 W; maximum of peak power duration is 20 seconds without asserting the
SMBAlert signal
7 Measured with a 10uF low ESR capacitor in parallel with a 0.1uF ceramic capacitor at the point of measurement
866.513.2839
tech.support@psbel.com
© 2015 Bel Power Solutions, Inc.
BCD.00478_AC