English
Language : 

PET1600-12-074NA Datasheet, PDF (4/25 Pages) Bel Fuse Inc. – AC input with power factor correction
PET1600-12-074NA
Stresses in excess of the absolute maximum ratings may cause performance degradation, adversely affect long-term
reliability, and cause permanent damage to the supply.
PARAMETER
Vi maxc Maximum Input Voltage
DESCRIPTION / CONDITION
Continuous
MIN NOM MAX UNIT
264
VAC
General Condition: TA = 0… 55 °C unless otherwise noted.
PARAMETER
Vi nom Nominal Input Voltage
Vi
Ii max
Ii inrush
fi
Input Voltage Ranges
Maximum Input Current
Inrush Current Limitation
Input Frequency
PF
Power Factor
THD
Vi on
Vi off
Total Harmonic Distortion
Turn-on Input Voltage1
Turn-off Input Voltage1
η
Efficiency2
TV1 holdup Hold-up Time V1
TVSB holdup Hold-up Time VSB
DESCRIPTION / CONDITION
Rated Voltage High Line (Vi nom HL)
Rated Voltage Low Line (Vi nom LL)
Normal operating (Vi min HL to Vi max HL), High Line
Normal operating (Vi min LL to Vi max LL), Low Line
VIN = 100VAC, 100% load
Vi min to Vi max, TNTC = 25°C, 5ms
10% Load
20% Load
50% Load
100% Load
TBD
Ramping up
Ramping down
VIN = 230VAC, 10% load
VIN = 230VAC, 20% load
VIN = 230VAC, 50% load
VIN = 230VAC, 100% load
VIN = 230VAC, 50% load
VIN = 230VAC, 75% load
VIN = 230VAC, 100% load
VIN = 110VAC, 100% load
12VSB, full load
MIN NOM MAX UNIT
200
230
240
VAC
100
115
127
VAC
180
264
VAC
90
140
VAC
13
ARMS
10
Ap
47
50/60
63
Hz
0.8
W/VA
0.9
W/VA
0.9
W/VA
0.95
W/VA
TBD
%
87
90
VAC
82
87
VAC
82
90.8
%
90
93.5
%
94
94.4
%
91
93.0
%
20
ms
13
ms
9
ms
17
ms
70
ms
Time-lag 16A input fuse (5 x 20 mm) in series with the L-line inside the power supply protects against severe defects. The
fuse is not accessible from the outside and is therefore not a serviceable part.
1 The Front-End is provided with a minimum hysteresis of 3V during turn-on and turn-off within the ranges
2 Efficiency measured without fan power per EPA server guidelines
866.513.2839
tech.support@psbel.com
© 2015 Bel Power Solutions, Inc.
BCD.00350_AC