English
Language : 

BPS40-12 Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – Maintenance Free(topping up not needed)
VRLA Rechargeable Battery
BPS40-12
Measures
Technology
Values
Innovation
FEATURES
APPLICATIONS
Maintenance Free ( topping up not needed )
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
SPECIFICATIONS
UPS
Telecom Systems
Switch Boards
Security Systems
Medical Systems
Photovoltaic Systems
Emergency Lighting
Golf Carts
Nominal Voltage
12 V
Nominal Capacity
40Ah @ 20 hour rate F.V.(1.75V/cell)
Approx. Weight
14300g(31.53lbs.)
Terminals
Internal Resistance
Max. Discharge Current
B2 (Fitting M5 bolt & nut) , I1 and I2 are optional
8m (Fully Charged )
600 A (5 sec.)
Max. Charge Current
Operating Temperature Range
12 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Container Material
Standard: ABS( UL 94-HB) BPS40-12
Optional: Flame Retardant ABS(UL 94-V0) BPS40-12FR
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
VdS G102110
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
197±1.5 (7.76±0.06)
Width
165±1.5 (6.50±0.06)
Container Height
171±1.5 (6.73±0.06)
Total Height
171±1.5 (6.73±0.06)
197 1.5 (7.76 0.06 )
165 1.5(6.50 0.06)
Terminal B2
15.0(0.59)
5.2(0.20)
Terminal I1
M5x0.8
Terminal I2
M6x1.0
[M5 BOLT & NUT]
[M5 BOLT & NUT]
[M6 BOLT]
Terminal Hardware Initial Torque: B2,I1(4.0Nm±5%),I2(5.5Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
1.80V
5 Min
1280
10 Min
1007
15 Min
811
30 Min
508
1 Hr
291.1
3 Hr
116.6
5 Hr
80.4
1.75V
1482
1091
848
527
299.9
118.9
81.6
1.70V
1575
1130
874
539
305.2
120.0
82.0
1.65V
1645
1157
894
547
308.9
120.8
82.3
1.60V
1700
1180
912
552
312.0
121.6
82.6
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
5 Min
10 Min
15 Min 30 Min
1 Hr
3 Hr
5 Hr
1.80V
115
88.6
70.5
43.0
24.46
9.72
6.70
1.75V
136
96.0
73.7
44.7
25.20
9.91
6.80
1.70V
144
99.5
76.0
45.7
25.65
10.00
6.84
1.65V
151
101.8
77.7
46.3
25.96
10.07
6.86
1.60V
156
103.9
79.3
46.8
26.22
10.13
6.88
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
44.93
45.60
45.83
45.96
45.96
20 Hr
23.64
24.00
24.12
24.19
24.19
10 Hr
3.74
3.80
3.82
3.83
3.83
20 Hr
1.97
2.00
2.01
2.02
2.02
For operation, please refer to the instruction from technical manual.