English
Language : 

BPS35-12F Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – Maintenance Free(topping up not needed)
VRLA Rechargeable Battery
BPS35-12 Finger Type
Measures
Technology
Values
Innovation
FEATURES
APPLICATIONS
Maintenance Free ( topping up not needed )
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
SPECIFICATIONS
UPS
Telecom Systems
Switch Boards
Security Systems
Medical Systems
Photovoltaic Systems
Emergency Lighting
Golf Carts
Nominal Voltage
12 V
Nominal Capacity
35.0Ah @ 20 hour rate F.V.(1.75V/cell)
Approx. Weight
11450g(25.25lbs.)
Terminals
Internal Resistance
Max. Discharge Current
B7 (Fitting M6 bolt & nut) I2 is optional
9m (Fully Charged )
525 A (5 sec.)
Max. Charge Current
Operating Temperature Range
10.5 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Container Material
Standard: ABS( UL 94-HB) BPS35-12
Optional: Flame Retardant ABS(UL 94-V0) BPS35-12FR
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
195±1.5 (7.68±0.06)
Width
129±1.5 (5.08±0.06)
Container Height
168±1.5 (6.61±0.06)
Total Height
B7:179±2.0 (7.05±0.08)
I2:168±2.0 (6.61±0.08)
195 1.5(7.68 0.06)
129 1.5(5.08 0.06)
Terminal B7
16.2(0.64)
6.2(0.24)
Terminal I2
M6x1.0
[M6 BOLT & NUT]
[M6 BOLT]
Terminal Hardware Initial Torque: B7/I2(5.5Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
(V/cell)
Time
1.80V
5 Min
1265
10 Min
932
15 Min
747
30 Min
444
1 Hr
254.7
3 Hr
102.0
5 Hr
70.3
1.75V
1465
1009
781
461
262.4
104.1
71.4
1.70V
1556
1045
805
472
267.1
105.0
71.8
1.65V
1626
1071
824
478
270.3
105.7
72.0
1.60V
1680
1092
840
483
273.0
106.4
72.3
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
114.0
82.0
64.9
37.6
21.4
8.50
5.86
1.75V
134.4
88.8
67.9
39.1
22.0
8.67
5.95
1.70V
142.8
92.0
70.0
40.0
22.4
8.75
5.98
1.65V
149.2
94.2
71.6
40.5
22.7
8.81
6.00
1.60V
154.1
96.1
73.0
40.9
22.9
8.86
6.02
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
39.31
39.90
40.10
40.22
40.22
20 Hr
20.69
21.00
21.11
21.17
21.17
10 Hr
3.28
3.32
3.34
3.35
3.35
20 Hr
1.72
1.75
1.76
1.76
1.76
For operation, please refer to the instruction from technical manual.