BPS3-12 Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – Maintenance Free(topping up not needed)
VRLA Rechargeable Battery
BPS3-12
Measures
Technology
Values
Innovation
FEATURES
Maintenance Free ( topping up not needed )
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
APPLICATIONS
UPS
Security Systems
Medical Equipment
Power Packs
Emergency Lighting
R/C Cars & Planes
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
Container Material
DIMENSION(mm/inch)
Length
134±1.5 (5.28±0.06)
Width
67±1.5 (2.64±0.06)
Container Height
60±1.5 (2.36±0.06)
Total Height
66±2.0 (2.60±0.08)
12 V
3.0Ah @ 20 hour rate F.V.(1.75V/cell)
1300g(2.87lbs.)
T1 (Faston Tab 187) T2 is optional
50m (Fully Charged )
45 A (5 sec.)
0.9 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Standard: ABS( UL 94-HB) BPS3-12
Optional: Flame Retardant ABS(UL 94-V0) BPS3-12FR
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
OUTER DIMENSIONS
TERMINAL TYPE
Terminal T1
3.2(0.13)
Terminal T2
3.4(0.13)
134±1.5(5.28±0.06)
67±1.5(2.64±0.06)
6.35(0.25)
7.95(0.31)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
1.80V
5 Min
108.5
10 Min
79.8
15 Min
64.0
30 Min
38.07
1 Hr
21.83
3 Hr
8.74
5 Hr
6.029
1.75V
125.5
86.5
66.9
39.52
22.49
8.92
6.120
1.70V
133.4
89.6
69.0
40.42
22.89
9.00
6.153
1.65V
139.4
91.8
70.6
40.99
23.17
9.06
6.175
1.60V
144.0
93.6
72.0
41.40
23.40
9.12
6.193
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
1.80V
5 Min
9.77
10 Min
7.03
15 Min
5.56
30 Min
3.23
1 Hr
1.835
3 Hr
0.729
5 Hr
0.502
1.75V
11.52
7.61
5.82
3.35
1.890
0.743
0.510
1.70V
12.24
7.89
6.00
3.43
1.924
0.750
0.513
1.65V
12.79
8.08
6.14
3.47
1.947
0.755
0.515
1.60V
13.21
8.24
6.26
3.51
1.966
0.760
0.516
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
3.369
3.420
3.437
3.447
3.447
20 Hr
1.773
1.800
1.812
1.812
1.812
10 Hr
0.281
0.285
0.286
0.287
0.287
20 Hr
0.148
0.150
0.151
0.151
0.151
For operation, please refer to the instruction from technical manual.