VRLA Rechargeable Battery
BPS200-12
Measures
Technology
Values
Innovation
FEATURES
Maintenance Free ( topping up not needed )
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
integrated Flame Arrestor at each cell
Carry Handles for easy installation
APPLICATIONS
UPS
Telecom Systems
Switch Boards
Photovoltaic Systems
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
Container Material
12 V
200Ah @ 20 hour rate F.V.(1.75V/cell)
61.5Kg(135.6lbs.)
B9 (Fitting M8 bolt & nut) I3 is optional
2.5m (Fully Charged )
800 A (5 sec.)
60 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Standard: ABS( UL 94-HB) BPS200-12
Optional: Flame Retardant ABS(UL 94-V0) BPS200-12FR
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
522±2.0 (20.55±0.08)
Width
202±2.0 (7.95±0.08)
Container Height
216±2.0 (8.50±0.08)
Total Height
B9:240±2.0 (9.45±0.08)
I3:220±2.0 (8.66±0.08)
522 ± 2 (20.55 ± 0.08)
202 ± 2 (7.95 ± 0.08)
Terminal B9
Terminal I3
M8x1.25
[M8 BOLT & NUT]
[M8 BOLT]
Terminal Hardware Initial Torque: B9,I3(10.0Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
3724
2537
1456
582.8
402.0
1.75V
3896
2634
1499
594.6
408.0
1.70V
4016
2694
1526
600.0
410.3
1.65V
4108
2731
1545
604.3
411.7
1.60V
4190
2760
1560
607.7
412.8
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
323.8
215.0
122.3
48.57
33.50
1.75V
338.8
223.2
126.0
49.55
34.00
1.70V
349.2
228.3
128.3
50.00
34.19
1.65V
357.2
231.5
129.8
50.36
34.31
1.60V
364.4
233.9
131.1
50.64
34.40
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
224.6
228.0
229.2
229.7
229.7
10 Hr
18.71
19.00
19.10
19.14
19.14
20 Hr
118.2
120.0
120.6
120.9
120.9
20 Hr
9.85
10.00
10.05
10.08
10.08
For operation, please refer to the instruction from technical manual.