English
Language : 

BPS160-12 Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – VRLA Rechageable Battery
VRLA Rechargeable Battery
BPS160-12
Measures
Technology
Values
Innovation
FEATURES
Maintenance Free ( topping up not needed )
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
integrated Flame Arrestor at each cell
Carry Handles for easy installation
APPLICATIONS
UPS
Telecom Systems
Switch Boards
Photovoltaic Systems
APPLICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
Container Material
12 V
160Ah @ 20 hour rate F.V.(1.75V/cell)
51.2Kg(112.9lbs.)
B9 (Fitting M8 bolt & nut) I3 is optional
2.7m (Fully Charged )
800 A (5 sec.)
48 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Standard: ABS( UL 94-HB) BPS160-12
Optional: Flame Retardant ABS(UL 94-V0) BPS160-12FR
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
483±2.0 (19.02±0.08)
Width
Terminal B9
Terminal I3
M8x1.25
171±2.0 (6.73±0.08)
Container Height
240±2.0 (9.45±0.08)
Total Height
240±2.0 (9.45±0.08)
[M8 BOLT & NUT]
[M8 BOLT]
Terminal Hardware Initial Torque: B9,I3(10.0Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
2933
2030
1165
466.3
321.6
1.75V
3068
2107
1199
475.7
326.4
1.70V
3163
2155
1221
480.0
328.2
1.65V
3235
2185
1236
483.4
329.4
1.60V
3300
2208
1248
486.2
330.3
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
255.0
172.0
97.9
38.86
26.80
1.75V
266.8
178.6
100.8
39.64
27.20
1.70V
275.0
182.7
102.6
40.00
27.35
1.65V
281.3
185.2
103.8
40.28
27.45
1.60V
287.0
187.1
104.9
40.52
27.52
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
180.0
182.4
183.3
183.8
183.8
10 Hr
15.00
15.20
15.28
15.32
15.32
20 Hr
94.8
96.0
96.5
96.7
96.7
20 Hr
7.90
8.00
8.04
8.06
8.06
For operation, please refer to the instruction from technical manual.
A/3 REV. May. 2016 Powered by B.B. Battery Co., Ltd.