English
Language : 

BPS12-6 Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – Maintenance Free(topping up not needed)
VRLA Rechargeable Battery
BPS12-6
Measures
Technology
Values
Innovation
FEATURES
APPLICATIONS
Maintenance Free ( topping up not needed )
Non - spillable ( no free electrolyte )
Low Self Discharge, less than 3% per month
both Vertical & Horizontal installations
SPECIFICATIONS
UPS
Security Systems
Medical Equipment
Power Packs
Emergency Lighting
R/C Cars & Planes
Laboratory Equipment
Nominal Voltage
Nominal Capacity
Approx. Weight
6V
12.0Ah @ 20 hour rate F.V.(1.75V/cell)
1980g(4.37lbs.)
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
T1 (Faston Tab 187) T2 is optional
9m (Fully Charged )
180 A (5 sec.)
3.6 A
Charge:0oC~40oC(32oF~104oF)
Discharge:-20oC~50oC(-4oF~122oF)
Storage.:-20oC~40oC(-4oF~104oF)
Container Material
Standard: ABS( UL 94-HB) BPS12-6
Optional: Flame Retardant ABS(UL 94-V0) BPS12-6FR
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
VdS G103023
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
151±1.5 (5.94±0.06)
Width
50±1.5 (1.97±0.06)
Container Height
94±1.5 (3.70±0.06)
Total Height
100±2.0 (3.94±0.08)
151 ± 1.5 (5.94 ± 0.06)
50 ± 1.5 (1.97 ± 0.06)
Terminal T1
3.2(0.13)
Terminal T2
3.4(0.13)
6.35(0.25)
7.95(0.31)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
1.80V
5 Min
216.9
10 Min
159.7
15 Min
128.0
30 Min
76.1
1 Hr
43.7
3 Hr
17.5
5 Hr
12.06
1.75V
251.1
173.0
133.9
79.0
45.0
17.8
12.24
1.70V
266.8
179.2
138.0
80.8
45.8
18.0
12.31
1.65V
278.8
183.5
141.2
82.0
46.3
18.1
12.35
1.60V
288.0
187.2
144.0
82.8
46.8
18.2
12.39
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
1.80V
5 Min
39.1
10 Min
28.1
15 Min
22.3
30 Min
12.9
1 Hr
7.34
3 Hr
2.91
5 Hr
2.010
1.75V
46.1
30.5
23.3
13.4
7.56
2.97
2.040
1.70V
48.9
31.6
24.0
13.7
7.70
3.00
2.051
1.65V
51.1
32.3
24.6
13.9
7.79
3.02
2.058
1.60V
52.8
33.0
25.0
14.0
7.87
3.04
2.064
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
6.74
6.84
6.87
6.89
6.89
20 Hr
3.55
3.60
3.62
3.63
3.63
10 Hr
1.123
1.140
1.146
1.149
1.149
20 Hr
0.591
0.600
0.603
0.605
0.605
For operation, please refer to the instruction from technical manual.