English
Language : 

BP180-6 Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – VRLA Rechargeable Battery
VRLA Rechargeable Battery
BP180-6
Measures
Technology
Values
Innovation
FEATURES
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity loss per month.
Can be used in any orientation(excluding used inverted).
Flame-arrestor is installed to ensure safety.
Absorbent Glass Mat technology for efficient gas recombination.
APPLICATION
UPS
Telecom
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
Container Material
6V
180Ah @ 20 hour rate F.V.(1.75V/cell)
28.8Kg(63.5lbs.)
B9 (Fitting M8 bolt & nut) I3 is optional
2.5m (Fully Charged )
800 A (5 sec.)
54 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Standard: ABS( UL 94-HB) BP180-6
Optional: Flame Retardant ABS(UL 94-V0) BP180-6FR
IEC 60896-21/22
JIS C 8704-2
GB/T 19638.2
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
260±2.0 (10.24±0.08)
Width
171±2.0 (6.73±0.08)
Container Height
220±2.0 (8.66±0.08)
Total Height
244±2.0 (9.61±0.08)
260 2.0(10.24 0.08)
171 2.0(6.73 0.08)
Terminal B9
Terminal I3
M8x1.25
[M8 BOLT & NUT]
[M8 BOLT]
Terminal Hardware Initial Torque: B9 ,I3(10.0Nm±5%)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
1732
1165
655.1
262.3
180.9
1.75V
1812
1209
674.6
267.6
183.6
1.70V
1868
1237
686.8
270.0
184.6
1.65V
1911
1254
695.1
271.9
185.3
1.60V
1949
1267
702.0
273.5
185.8
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
(V/cell)
Time
1.80V
15 Min
301.2
30 Min
197.4
1 Hr
110.1
3 Hr
43.71
5 Hr
30.15
1.75V
315.1
204.9
113.4
44.59
30.60
1.70V
324.8
209.6
115.4
45.00
30.77
1.65V
332.3
212.5
116.8
45.32
30.88
1.60V
339.0
214.7
118.0
45.58
30.96
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
101.1
102.6
103.1
103.4
103.4
10 Hr
16.84
17.10
17.19
17.23
17.23
20 Hr
53.33
54.00
54.27
54.41
54.41
20 Hr
8.89
9.00
9.05
9.07
9.07
A/2 REV. Mar. 2013
Powered by B.B. Battery Co., Ltd.