SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
Container Material
6V
13.0Ah @ 20 hour rate F.V.(1.75V/cell)
2500g(5.51lbs.)
Type H
9m (Fully Charged )
30 A (5 sec.)
3.9 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
ABS(UL94-HB, UL94-V0 is optional)
ISO 9001
ISO14001
UL
CE
IEC61056
JIS C 8702
GB/T 19639
DIMENSION(mm/inch)
OUTER DIMENSIONS
TERMINAL TYPE
Length
108±1.5 (4.25±0.06)
Width
71±1.5 (2.80±0.06)
Container Height
140±1.5 (5.51±0.06)
Total Height
140±1.5 (5.51±0.06)
Terminal H
9.5(0.37)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
138.6
82.5
47.3
18.9
13.06
7.30
3.84
1.75V
145.0
85.6
48.7
19.3
13.26
7.41
3.90
1.70V
149.5
87.6
49.6
19.5
13.33
7.45
3.92
1.65V
152.9
88.8
50.2
19.6
13.38
7.47
3.93
1.60V
156.0
89.7
50.7
19.8
13.42
7.47
3.93
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
15 Min
30 Min
1 Hr
3 Hr
5 Hr
10 Hr
20 Hr
1.80V
24.1
14.0
7.95
3.16
2.177
1.217
0.640
1.75V
25.2
14.5
8.19
3.22
2.210
1.235
0.650
1.70V
26.0
14.8
8.34
3.25
2.222
1.241
0.653
1.65V
26.6
15.1
8.44
3.27
2.230
1.245
0.655
1.60V
27.1
15.2
8.52
3.29
2.237
1.245
0.655