English
Language : 

BP1.0-6-T1 Datasheet, PDF (1/1 Pages) B. B. Battery Co., Ltd. – VRLA Rechargeable Battery
VRLA Rechargeable Battery
BP1.0-6
Measures
Technology
Values
Innovation
FEATURES
Maintenance free(no water topping-up required).
No free acid(Non-spillable battery).
Low self-discharge rate, lower than 3% capacity loss per month.
Can be used in any orientation(excluding used inverted).
Absorbent Glass Mat technology for efficient gas recombination.
APPLICATION
UPS
Security
Medical
Lojack
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Internal Resistance
Max. Discharge Current
Max. Charge Current
Operating Temperature Range
Container Material
DIMENSION(mm/inch)
Length
51±1.5 (2.01±0.06)
Width
42±1.5 (1.65±0.06)
Container Height
51±1.5 (2.01±0.06)
Total Height
56±2.0 (2.20±0.08)
6V
1.0Ah @ 20 hour rate F.V.(1.75V/cell)
250g(0.55lbs.)
T1 (Faston Tab 187)
65m (Fully Charged )
15 A (5 sec.)
0.3 A
Charge 0oC~40oC(32oF~104oF)
Discharge -20oC~50oC(-4oF~122oF)
Storage. -20oC~40oC(-4oF~104oF)
Standard: ABS( UL 94-HB) BP1.0-6
Optional: Flame Retardant ABS(UL 94-V0) BP1.0-6FR
IEC 61056-1
JIS C 8702-1
GB/T 19639.1
OUTER DIMENSIONS
TERMINAL TYPE
51 1.5(2.01 0.06)
42 1.5(1.65 0.06)
Terminal T1
3.2(0.13)
6.35(0.25)
Constant power discharge characteristics at 25 oC/77 oF Unit: W
Discharge
F.V.
Time
(V/cell)
5 Min
10 Min
15 Min
30 Min
1 Hr
3 Hr
5 Hr
1.80V
18.08
13.31
10.66
6.35
3.639
1.457
1.005
1.75V
20.92
14.42
11.15
6.59
3.748
1.487
1.020
1.70V
22.23
14.94
11.50
6.74
3.816
1.500
1.026
1.65V
23.23
15.29
11.76
6.83
3.861
1.510
1.029
1.60V
24.00
15.60
12.00
6.90
3.900
1.520
1.032
Constant current discharge characteristics at 25 oC/77 oF Unit: A
Discharge
F.V.
Time
(V/cell)
5 Min
10 Min
15 Min 30 Min
1 Hr
3 Hr
5 Hr
1.80V
3.26
2.34
1.85
1.075
0.612
0.243
0.167
1.75V
3.84
2.54
1.94
1.116
0.630
0.248
0.170
1.70V
4.08
2.63
2.00
1.142
0.641
0.250
0.171
1.65V
4.26
2.69
2.05
1.158
0.649
0.252
0.172
1.60V
4.40
2.75
2.09
1.169
0.655
0.253
0.172
All data and artworks shall be changed without prior notice, BB reserves the right to explain and update the information contained hereinto.
10 Hr
0.562
0.570
0.573
0.575
0.575
20 Hr
0.296
0.300
0.300
0.300
0.300
10 Hr
0.094
0.095
0.095
0.096
0.096
20 Hr
0.049
0.050
0.050
0.050
0.050
A/2 REV. Mar. 2013