English
Language : 

BC10-12-T2 Datasheet, PDF (1/2 Pages) B. B. Battery Co., Ltd. – VRLA Rechargeable Battery
VRLA Rechargeable Battery
BC10-12
Measures
Technology
Values
Innovation
FEATURES
Maintenance free(no water topping-up required)
No free acid(Non-spillable battery)
Can be used in any orientation(excluding used inverted)
Absorbent Glass Mat technology for efficient gas recombination
Its design life is up to 5 years in floating application
APPLICATION
UPS
Laboratory
Equipment
SPECIFICATIONS
Nominal Voltage
Nominal Capacity
Approx. Weight
Terminals
Max. Discharge Current
Max. Charge Current
Operating Temperature
Range
Self Discharge
Internal Resistance
12V
20 Hour Rate (500mA, 10.5V)
10 Hour Rate (950mA, 10.5V)
5 Hour Rate (1700mA, 10.5V)
1 Hour Rate (6000mA, 9.30V)
10.0 Ah
9.50 Ah
8.50 Ah
6.00 Ah
3000g(6.61lbs.)
T2 (Faston Tab 250) T1 is optional
150 A (5 sec.)
3.00 A
Charge
Discharge
Storage
0oC~40oC(32oF~104oF)
-20oC~50oC(-4oF~122oF)
-20oC~40oC(-4oF~104oF)
< 3% per month (25oC)
17m (Fully Charged )
CONTAINER MATERIAL
Standard: ABS( UL 94-HB)
Model: BC10-12 (Dark gray color)
Optional: ABS(UL 94-V0)
Model: BC10-12FR (Light gray color)
UL
IEC 61056-1
GB/T 19639.1
CE
JIS C 8702-1
OUTER DIMENSIONS mm(inch)
Length (L)
Width (W)
Container Height (H) Total Height (TH)
151±1.5(5.94±0.06) 65±1.5(2.56±0.06) 112±1.5(4.41±0.06) 117±2.0(4.61±0.08)
151 1.5(5.94 0.06)
65 1.5(2.56 0.06)
TERMINAL TYPE
Terminal T1
3.2(0.13)
Terminal T2
3.4(0.13)
6.35(0.25)
7.95(0.31)