English
Language : 

IFLOW-200 Datasheet, PDF (1/1 Pages) Advanced Thermal Solutions, Inc. – MEASURE THE THERMAL AND HYDRAULIC PERFORMANCE OF COLD PLATES
COLD PLATE CHARACTERIZATION SYSTEM
iFLOW-200TM
MEASURE THE THERMAL & HYDRAULIC PERFORMANCE OF COLD PLATES
FEATURES:
FEATURES & BENEFITS
The iFLOW-200TM system
measures the thermal and
hydraulic characteristics of
a cold plate. It replaces the
complex process of varying
the volumetric flow rate of
the coolant, and measuring
the pressure drop and
temperature of the cold
plate. iFLOW-200TM users
simply set up the starting
flow, ending flow, number
of test points, dwell time,
power applied to the cold
plate and other parameters
in the coolingVIEWTM
software and run the
application.
» iFLOW-200™ measures a cold plate’s inlet/outlet fluid
temperature, surface temperature, coolant volumetric
flow rate and pressure drop by providing different flow
rates to the cold plate.
» iFLOW-200™ measures coolant temperature
from 0-70oC with accuracy of +/-1oC, using K-type
thermocouples. Distilled water is used as the reference
coolant.
OVERALL DIMENSIONS (D x W x H)
365 mm x 425 mm x 120 mm
MAXIMUM VOLUMETRIC FLOW RATE
4.5 liter/min
FLOW TEMPERATURE RANGE
0 to 70 oC
» iFLOW-200™ measures cold plate differential pressure
up to 103,000 Pa (15 psi) with pressure measurement
of +/-1% of full scale.
» iFLOW-200™ features a separate control box and
hydraulics units with USB connections.
» iFLOW-200™ includes user-friendly coolingVIEW™
application software that automates the testing of a cold
plate by setting the required parameters.
» iFLOW-200™software, coolingVIEWTM, calculates
thermal resistance and pressure drop of the cold plate
as a function of flow rate for selected liquids other than
distilled water.
SURFACE TEMPERATURE RANGE
0 to 200 oC
DIFFERENTIAL PRESSURE RANGE
+/- 103,000 Pa(15 psi)
PRESSURE ACCURACY
+/- 1% of full scale
TEMPERATURE ACCURACY
+/- 1 oC
FLOW RATE ACCURACY
+/-1% of full scale
SOFTWARE
coolingVIEWTM
For further technical information, please contact Advanced Thermal
Solutions, Inc. at 1-781-769-2800 or www.qats.com
FLUID LEVEL INDICATOR
INLET/OUTLET OF THE
COLD PLATE
SENSOR PORTS
COOLING SYSTEM FOR THE
INTERNAL HEAT EXCHANGER
APPLICATION DOMAIN
» Evaluating and
troubleshooting different
cold plate models
» Simulating different
applications and conditions
» Optimizing flow and thermal
performance
» Testing alternative liquids
» Free Lifetime Tech Support
89-27 ACCESS ROAD, NORWOOD, MA 02062 USA | T: 781.769. 2800 F: 781.769.9979 | WWW.QATS.COM
R2_0215