MPS-200 Datasheet, PDF (1/4 Pages) Astrodyne Corporation – 200W 1~4 Output for Medical Type
2 0 0 W 1 ~ 4 O u t p u t1~f o4�rOMutepudti�cMaeldiTcyapl Teype
m2 0p0sW/�d�M/etd/iqc-a2l 0se0riesseries
Specification
AC�INPUT�VOLTAGE
90~264�VAC,�47~440Hz�/�127~370VDC.
POWER�FACTOR�(Typ.)
PF>0.95/230VAC����������PF>0.98/115VAC�at�full�load
AC�INPUT�CURRENT (Typ.)
Maximum�input�current�3.5A at�115VAC,�60Hz�or
1.6A at�230VAC,�60Hz�with�100%�output�load.
INRUSH�CURRENT (Typ.)
Inrush�current�is�less�than�25A at�115VAC�or
less�than�40A at�230VAC�under�cold�start
conditions.�Limiting�provided�by�internal
thermistors.
SETUP,�RISE�TIME
1000ms,�20ms�/�230VAC at�full�load
3000ms,�20ms�/�115VAC�at�full�load
HOLD-UP TIME (Typ.)
16ms�/�230VAC�at�full�load
16ms�/�115VAC�at�full�load
LEAKAGE�CURRENT
Leakage�current�is�less�than�180 A at�264VAC�for
earth�leakage�current
Leakage�current�is�less�than�100 A at�264VAC�for
patient�leakage�current
DC�OUTPUT ADJ.�RANGE
DC�output�voltage�(or�CH1�of�multiple�output�models)
can�be�adjusted�between�-5%~+10%�rated�output
voltage�by�potential�meter.
OVER�LOAD�PROTECTION
Fully�protected�against�short�circuit�and�output�overload.
The�hiccup�type�protection�will�be�activated�at�120~160%
rated�load�and�recovers�automatically�after�fault�condition
is�removed.
OVER�VOLTAGE�PROTECTION
Provided�on�output�channel�1�only�at�115%~135%
rated�output�voltage.
Output�will�be�shut�down�when�this�protection�is�activated.
OVER�TEMPERATURE�PROTECTION
When�the�temperature�of TSW1�which�detect on�heat�sink�of
power�transistor�reaches�95 This�protection�is�activated.
Then�output�will�be�shut�down�and�recovers�automatically
after�temperature�goes�down.
POWER�GOOD�/�FAIL SIGNAL
TTL logic�high�for�power�good�and TTL low�for
power�fail.�When�the�output�voltage�reaches�90%�of
rated�value,�a�+5V TTL signal�will�be�sent�out�with�a
10~500ms�delay; At�least�1ms�before�the�output
voltage�goes�below�90%�of�the�rated�value,�the TTL
signal�will�be�turned�off.
*�MPS-200-3.3�does�not�have�this�function.
REMOTE�CONTROL
RC+/RC-:0�~�0.8V=power�on;�4�~�10V=power�off�sink�current<4~10mA
Features
Universal AC�input�/�Full�range
Low�leakage�current�<180 A
Protections:Short�circuit/Over�load/Over�voltage/Over�temperature
Free�air�convection�for�140W�and�forced�air�convection�for�200W
UL2601-1�medical�safety�approved
With�power�good�and�fail�signal�output
Built-in�remote�ON-OFF�control
Built-in�remote�sense�function
Fixed�switching�frequency�at�100KHz
3�years�warranty
WORKING�TEMP.
Whole�series�can�operate�from�-20~70 .�Please�refer
to�the�derating�curves.
WORKING�HUMIDITY
20~90%�RH�non-condensing.
STORAGE�TEMP.,�HUMIDITY
-40~+85 ,�10~90%�RH
TEMP.�COEFFICIENT
0.04%/ on�all�outputs�at�full�load�between�0~50 of�ambient�temperature.
VIBRATION
2G�of�acceleration,�vibrating�frequency�adjust�from�10Hz�~500Hz�within�a
10-minute�cycle.�6�testing�cycles�(60�minutes)�each�along�X, Y,�Z�axes.
SAFETY STANDARDS
Medical : UL2601-1, TUV�EN60601-1�approved
Commercial�: Also�design�refer�to�UL60950-1, TUV�EN60950-1
WITHSTAND�VOLTAGE
4000VAC�between�input�and�output
1500VAC�between�input�and�F.G.
500VAC�between�output�and�F.G.
ISOLATION�RESISTANCE
>100M�Ohms�for�I/P-O/P,�I/P-FG,�O/P-FG�by�using�500VDC�test�voltage.
EMI�COMPLIANCE
EMI�Specifications
Conducted�&�Radiation
Harmonic�distortion
Voltage�flicker
Compliance�Level
EN55011,�Class�B
EN55022,�Class�B
EN61000-3-2
EN61000-3-3
EMS�COMPLIANCE
EMS�Specification
ESD�air
ESD�contact
RF�field�susceptibility
EFT(Electrical�Fast Transient)/Burst
Lightning/Surge
Conducted�RF�susceptibility
Magnetic�field�immunity
Voltage�dip,�interruption
Digital�phone�carrier�immunity
MTBF
262,100�hours�min.�at�full�load�and�25
calculated�per�MIL-HDBK-217F.
Compliance�Level
EN61000-4-2, Level�3,�8KV
EN61000-4-2, Level�2,�4KV
EN61000-4-3, Level�2,�3V/m
Level�3,�10V/m
EN61000-4-4, Level�2,�1KV/5KHz
Level�3,�2KV/5KHz
EN61000-4-5, Level�4,�2KV/Line-Line
4KV/Line-Earth
EN61000-4-6, Level�2,�3Vrms/m
Level�3,�10Vrms/m
EN61000-4-8, Level�2,�3A/m
Level�3,�10A/m
EN61000-4-11,Compliance
ENV50204, Level�2,�3V/m,�900MHz
Level�3,�10A/m,�900MHz
of�ambient��temperature,
DIMENSION�(L*W*H)
177.8x107.95x35.5mm�or�7"x4.25"x1.4"
PACKING
0.66Kg;�24pcs/16.8Kg/1.04CUFT
WWW.ASTRODYNE.COM