AP6C64AA Datasheet, PDF (1/1 Pages) Astec America, Inc – 48V 400-600 Amp, Breaker Panel (BIP) | |||
|
48V 400-600 Amp
Breaker Panel (BIP)
AP6C64AA
A breaker interface panel, also knows as a power distribution unit
(PDU), or frame supervisory panel (FSP), improves system power
stability and provides a convenient centralized location for all
customer load circuit breakers, alarms, and filtering.
INPUT
AMERICAS
5810 Van Allen Way
Carlsbad, CA 92008
Telephone: 760-930-4600
Facsimile: 760-930-0698
EUROPE
Astec House, Waterfront Business Park
Merry Hill, Dudley
West Midlands, DY5 1LX, UK
Telephone: 44 (1384) 842-211
Facsimile: 44 (1384) 843-355
ASIA
Units 2111-2116, Level 21
Tower1, Metroplaza
223, Hing Fong Road
Fwai Fong, New Territories
Hong Kong
Telephone: 852-2437-9662
Facsimile: 852-2402-4426
Electrical Specs
DC input
-40 VDC to â75 VDC
Transients
Input feeds
ANSI T1.315-1994, FTZ19, BTR2511
4 x 100A each
4 x 150A each (available in the future)
Special Features
⢠Low profile:
⢠Fits in 2U height,
⢠3.47", 88.1 mm
⢠23" width
⢠4 x 100 A input feeds, upgradeable to 4 x 150A
input feeds
⢠supports A & B redundant input feeds
⢠4 hot swappable Breaker Modules + one Alarm
Module
⢠Breaker Modules available in various configurations,
all come equipped with:
⢠28,200 µF capacitor bank
⢠automatic inrush current limiting
⢠hot swappable, field replaceable without
service interruption
⢠Breaker Module configurations:
⢠5A 5A 5A 5A 5A
⢠20A 20A 20A 20A 20A
⢠25A 25A 5A 25A 25A
⢠10A 5A 30A 5A 10A
⢠25A 25A 25A 25A 25A
⢠30A 30A 5A 30A 30A
⢠other configurations available on request,
please consult your Astec representative
⢠Standard Alarm module comes equipped with:
⢠isolated alarm contacts
⢠input feed fail alarm
⢠output breaker trip alarm
⢠critical, major, minor alarms
⢠end aisle lamp drive
⢠fully programmable, 6 bit, shelf ID
⢠LED test switch
⢠connections for voice and data jacks
⢠Enhanced, customized alarm modules available by
special order
OUTPUT
DC output
Alarm signals
20 x 25A breakers total
Four breaker modules,
each with 5 x 25A breakers
Critical, major, minor alarms
Environmental
EMC/EMI:
No switching components, inherently
EMI/EMC benign
ESD:
Bellcore GR-1089-CORE, ETSI 300 386-1,
(15kV)
Operating Temperature and Humidity
-5°C to +55°C normal, 5% to 85% RH, non-condensing
-8°C to +65°C short term
Shock and
Vibration:
Bellcore GR-063-CORE and ETSI 300 019
Zone 4 earthquake
Fire Resistance: UL94V-0
UL
CSA
EN
Bellcore
Safety
1950
C22.2 950
60850, 41003
GR-063-CORE
182 Americaâs (USA): 1-888-41-ASTEC
Europe (UK): 44 (1384) 842-211 Asia (HK): 852-2437-9662
rev 12.01.01
|