DS800SL Series Data Sheet
STATUS INDICATIONS
See table below for Summary of Status signals, Ports and Indicators. The condition column assumes 2 or more power supplies present
and ON and 5.0 Vsb shared for management interface. On the “Fan Blocked” condition, the assumption is that all outputs are within spec
and not over temperature. This would be considered a “warning” condition. On the “Standby” condition, the system differentiates this state
by knowing PS_ONL in negated (requesting Standby).
Status Indicators
Condition
Normal Operation
V1 12 V Overcurrent
AC Input Fail
Fan Blocked or Running Under Speed.
O/P’s ok
UV on V1 12 V and PS Has Latched Off
UV on Vsb +5.0 and PS Has Turned Off
OV on V1 12V or Vsb +5.0 & PS Has
Latched Off
Over Temp and PS Has Turned Off
Fan Below Shutdown Limit
No Problems But PS is in Standby Mode
Status Signals
ACOK/L PWOK/H
0
1
0
0
1
0
0
1
Status Register
PSON PWOK
1
1
1
0
1
0
1
1
Fan-Fail
0
0
0
0
Shutdown Register
LED’s
AC-Loss 0-Temp 0-Current Fail AC DC Fail
0
0
0
0 On On Off
0
0
1
1 On Off On
1
0
0
1 Off Off Off
0
0
0
0 On On Off
0
0
1
0
0
0
0
0
1 On Off On
0
0
1
0
0
0
0
0
1 On Off On
0
0
1
0
0
0
0
0
1 On Off On
0
0
1
0
0
0
1
0
1 On Off On
0
0
1
0
1
0
0
0
1 On Off On
0
0
0
0
0
0
0
0
0 On Off Off
Output Connector and Pin Out Table
Pin
Signal Name
Pin 1
+12 V
Pin 2
+12 V
Pin 3
Ground
Pin 4
Ground
S1
+12 V Sense
S2
+12 V RTN Sense
S3
+12 V Current Share
S4
SMB_ALERT/L
S5
SDA
S6
SCL*
S7
PSKILL
S8
PSON/L
S9
PW_OK
S10
PS_A1
S11
+5.0 V_STBY
S12
+5.0 V_STBY
S13
Reserved
S14
PRESENT/L
S15
PS_A0
S16
Reserved
S17
Reserved for factory use
S18
EEPROM_WP
S19
ACOK/L
S20
Not used
S21
PS_A2
S22
V_STBY Remote Sense
S23
V_STBY
S24
V_STBY
* Supports I2C standard mode (100 kHz) only
Top Side
Ground
P3
Ground
P4
P1
+12V
Bottom Side
P2
+12V
Note: Pin number may not necessarily match vendor’s pin number
assignment. Please follow the signal and number assignment as
indicated in this datasheet