English
Language : 

EXQ125 Datasheet, PDF (2/2 Pages) Artesyn Technologies – 36-100W High Efficiency DC/DC Converters
EXQ125 Series
Single output
DC/DC CONVERTERS 36-100W High Efficiency DC/DC Converters
2
For the most current data and application support visit www.artesyn.com/powergroup/products.htm
OUTPUT
POWER
(MAX.)
36W
45W
54W
75W
82.5W
100W
100W
INPUT
VOLTAGE
33-75VDC
33-75VDC
33-75VDC
33-75VDC
33-75VDC
33-75VDC
33-75VDC
OVP
1.45VDC
1.8VDC
2.3VDC
3VDC
3.9VDC
6VDC
14.4VDC
OUTPUT
VOLTAGE
1.2V
1.5V
1.8V
2.5V
3.3V
5V
12V
OUTPUT
CURRENT
(MIN.)
0A
0A
0A
0A
0A
0A
0A
OUTPUT
CURRENT
(MAX.)
30A
30A
30A
30A
25A
20A
8.3A
EFFICIENCY
(TYP.)
86.5%
87.5%
88.0%
90.0%
91.0%
92.0%
93.0%
REGULATION
LINE LOAD
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
±0.2%
±0.2%
±0.2%
±0.2%
±0.2%
±0.2%
±0.2%
MODEL
NUMBER (7,8,9)
EXQ125-48S1V2
EXQ125-48S1V5
EXQ125-48S1V8
EXQ125-48S2V5
EXQ125-48S3V3
EXQ125-48S05
EXQ125-48S12
Notes
1 di/dt = 0.1A/µs, Vin = 48VDC, Tc = 25°C, load change = 0.5 lo max. to 0.75
lo max. and 0.75 lo max. to 0.5 lo max. Deviation varies by model, see
Long Form Data Sheet.
2 The EXQ125 meets level A and level B conducted emissions only with
external components connected before the input pins to the converter.
See Application Note 118.
3 Recommended input fusing is a 5A HRC 200V rated fuse.
4 This product is only for inclusion by professional installers within other
equipment and must not be operated as a stand alone product.
5 Measured with no external Pi filter. Significant reduction possible with
external filter. See Application Note 118.
6 Start-up into resistive load.
7 Active low remote On/Off is available. Standard product is active high.
When ordering active low parts, designate with the Suffix ‘-R’,
e.g EXQ125-48S3V3-R.
8 When ordering 0.145" pin lengths designate with the Suffix ‘-N’, if the
product is already a ‘-R’ suffix product then the suffix will be ‘-RN’
9 When ordering 0.110" pin lengths designate with the Suffix ‘-K’, if the
product is already a ‘-R’ suffix product then the suffix will be ‘-RK’
PIN CONNECTIONS
PIN NUMBER
FUNCTION
1
+Vin
2
On/Off
3
-Vin
4
-Vout
5
-Sense
6
Trim
7
+Sense
8
+Vout
International Safety Standard Approvals
TÜV
UL/cUL : UL1950 File No. E135734
TÜV Rheinland Certificate No. R2172600
CB Scheme No. US-TUVR-0982
PROTECTION
Short circuit protection
Overvoltage protection
TELECOM SPECIFICATION
Central office interface A
Continuous
Non-latching clamp
ETS300-132-2, input voltage
and current requirements
CAUTION: Hazardous internal voltages and high temperatures.
Ensure that unit is not user accessible.
Ø0.040 [Ø1.09]
(6 PLS)
0.815 [20.70 ]
0.515 [13.08 ]
0.215 [5.4 ]
2.000 [50.80]
3
4
5
2 Bottom View 6
1
7
8
Ø0.060 [Ø1.52]
(2 PLS)
0.815 [20.70]
0.665 [16.89]
0.515 [13.08]
0.365 [9.27]
0.215 [5.46]
0.000 [0.00]
0.50 [12.70]
M3 x 0.5 Threaded
Through (4 PLS)
0.070 [1.78]
2.280 [57.91]
*0.20 [5.08]
*Standard available pin length.
0.145 (3.68) and 0.110 (2.79)
options also available. (See
Notes 8 and 9 for ordering details)
1.030
[26.16]
0.210 [5.33]
0.210 [5.33]
1.030 [26.16]
0.815 [20.70]
0.515 [13.8 ]
0.215 [5.36 ]
0.000 [0.00]
Top View
1.450
[36.83]
ALL DIMENSIONS IN INCHES [mm]
1.860 [47.24]
0.070
[1.78]
Ø0.073 [Ø1.85]
(2 PLS)
1
8
7
2
6
3
5
4
Recommended
Hole Pattern
0.815 [20.70]
0.665 [16.89]
0.515 [13.08]
0.365 [9.27]
0.215 [5.46]
0.000 [0.00]
Ø0.128 [Ø3.25]
(4 PLS)
Data Sheet © Artesyn Technologies® 2002
The information and specifications contained in this data sheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising
from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompany the sale of any such product(s) or information contained herein.
Please consult our website for the following items: Application Note Longform Data Sheet
www.artesyn.com
File Name: EXQ125S.PDF Rev: 18 June 2002