English
Language : 

EXB100 Datasheet, PDF (2/2 Pages) Artesyn Technologies – 54-100W DC/DC Isolated Converters
EXB100 Series
Single output
DC/DC CONVERTERS 54-100W DC/DC Isolated Converters
For the most current data and application support visit www.artesyn.com/powergroup/products.htm
2
NEW Product
OUTPUT
POWER
(MAX.)
100W
100W
54W
INPUT
VOLTAGE
36-75VDC
36-75VDC
36-75VDC
OVP
6.0VDC
3.9VDC
2.2VDC
OUTPUT
VOLTAGE
5.0V
3.3V
1.8V
OUTPUT
CURRENT
(MIN.)
0A
0A
0A
OUTPUT
CURRENT
(MAX.)
20A
30A
30A
EFFICIENCY
(TYP.)
91.5%
90.5%
87.5%
REGULATION
LINE LOAD
±0.2%
±0.2%
±0.2%
±0.4%
±0.4%
±0.4%
MODEL
NUMBER (9)
EXB100-48S05
EXB100-48S3V3
EXB100-48S1V8
Notes
1 Measured as per recommended set-up. See Application Note 129 for details.
2 di/dt = 0.1A/µs, Vin = 48VDC, Tc = 25°C, load change = 0.5 lo max. to 0.75
lo max. and 0.75 lo max. to 0.5 lo max.
3 Recommended input fusing is a 5A HRC 200V rated fuse.
4 Measured with external filter. See Application Note 129 for details.
5 Signal line assumed <3m in length.
6 Start-up into resistive load.
7 The EXB100 meets levels A and B conducted emissions with external
components. See Application Note 129 for details.
8 This product is only for inclusion by professional installers within other
equipment and must not be operated as a stand alone product.
9 Negative remote ON/OFF option also available. Add suffix ‘-R’ to part
number, for example EXB100-48S3V3-R.
PROTECTION
Short circuit protection
Overvoltage protection
TELECOM SPECIFICATION
Central office interface A
Continuous
Non-latching clamp
ETS300-132-2 input voltage
and current requirements
CAUTION: Hazardous internal voltages and high temperatures.
Ensure that unit is not user accessible.
PIN CONNECTIONS
PIN NUMBER
FUNCTION
1
-Vin
2
No Pin
3
Remote ON/OFF
4
+Vin
5
+Vout
6
+Sense
7
Trim
8
-Sense
9
-Vout
International Safety Standard Approvals
TÜV
UL/cUL CAN/CSA 22.2 No. 60950-00 : UL 60950
File No. E174104
TÜV Product Service. Certificate No. B 02 02 38572 031
Max open-frame
converter height
seating plane
Ø0.040 ±0.002
(Ø1.02 ±0.05)
6 Places Ø0.080 ±0.002
Minimum clearance from
seating plane to
(Ø2.03 ±0.05)
2 Places
underside components
All dimensions in inches (mm)
General tolerance ±0.01in (±0.25mm)
except where specified otherwise
2.280±0.02
(57.91±0.5)
Vin-
Remote
ON/OFF
Vin+
1.900
(48.26)
Vo-
Sense-
Trim
Sense+
Vo+
Bottom View
Data Sheet © Artesyn Technologies® 2002
The information and specifications contained in this data sheet are believed to be correct at time of publication. However, Artesyn Technologies accepts no responsibility for consequences arising
from printing errors or inaccuracies. Specifications are subject to change without notice. No rights under any patent accompany the sale of any such product(s) or information contained herein.
Please consult our website for the following items: Application Note Longform Data Sheet
www.artesyn.com
File Name: EXB100S.PDF Rev: 29 March 2002