English
Language : 

DS1600SPE Datasheet, PDF (2/8 Pages) Artesyn Technologies – 1600 Watts Distributed Power System
DS1600SPE Data Sheet
Electrical Specifications
Output
Main DC Output
Nominal setting
Total output regulation range
Dynamic load regulation range5
Output ripple
Output current
MIN
-0.20%
11.4 V
11.4 V
2 A4
NOM
12
Current sharing
Capacitive loading
Start-up from AC to output
Output rise time
Standby DC Output
Nominal setting
Total output regulation range
Dynamic load regulation range
Output ripple
Adjustment range
Output current
Current sharing
Capacitive loading
Start-up from AC to output
Output rise time
2,250 µF
2 ms
-3%
11.4 V
11.4 V
0.1 A4
47 µF
20 ms
2 ms
Within +/-5% of full load rating
12
N/A
N/A
Protections
Main Output
Overcurrent protection2
115%
Overvoltage protection1
13.5 V
Undervoltage Protection
10.5 V
Overtemperature protection
Yes
Fan fault protection
Yes
Standby Output
Overcurrent Protection3
120%
Overvoltage Protection1
13.5 V
Undervoltage Protection
10.0 V
1 Latch mode
2 Autorecovery if the overcurrent is less than 115% and last only for <500 ms
3 Standby protection is auto-recovery
4 Minimum current for transient load response testing only. Unit is designed to operate and be within output regulation range at zero load.
5 Maximum step size of 67 A at 0.5A/µs, with a beginning load of 8 A, and 3,350 µF capacitance
MAX
0.20%
12.6 V
12.6 V
150 mVp-p
133.33 A
14,000 µF
2,300 ms
60 ms
3%
12.6 V
12.6 V
150 mVp-p
3.5 A
1,000 µF
2,000 ms
60 ms
150%
15.0 V
11.0 V
150%
15.0 V
11.0 V