LPS52-M Datasheet, PDF (1/3 Pages) Artesyn Technologies – Total Power: 55 - 60 Watts | |||
|
POWER
Data Sheet
LPS50-M Series
60 Watts
Total Power: 55 - 60 Watts
Input Voltage: 90 - 264 Vac
127 - 300 Vdc
# of Outputs: Single
SPECIAL FEATURES
ÂÂ Medical safety approvals
ÂÂ Universal input
ÂÂ 2â x 4â footprint
ÂÂ Less than 1U high
ÂÂ Remote sense
ÂÂ Overload and short circuit protection
ÂÂ Adjustable output voltage
ÂÂ High efficiency
ÂÂ High MTBF
ÂÂ Built in EMI filter (CISPR 22 Class B)
ÂÂ LED power good indicator
ÂÂ Input power < 74 watts
ÂÂ Complies with EN61000-3-2
ÂÂ RoHS compliant
ÂÂ UL Class I approved
ÂÂ LPX100 enclosure kit available
ÂÂ Dual AC fuses
SAFETY
ÂÂ UL
ÂÂ CSA
ÂÂ VDE
ÂÂ CE
UL 60601-1
CSA-C22.2 No. 601.1-M90
EN60601-1
LVD & EMC
Electrical Specifications
Input
Input range
90 - 264 Vac (wide range)
127 - 300 Vdc
Frequency
47 - 440 Hz
Inrush current
<60 A peak @ 230 Vac, cold start @ 25 °C
Input power
<74 Watts
Efficiency
80 - 85% typical at full load
EMI/RFI
FCC Class B conducted; CISPR22 Class B conducted; EN55022 Class
B conducted; VDE0878PT3 Class B conducted.
Safety ground
leakage current
275 μA @ 50/60 Hz; 264 Vac input
Output
Maximum power
60 W for convection (LPS52 is 55 W)
Adjustment range
+20% minimum
Hold-up time
10/20 ms 115/230 Vac input line
Overload protection
Short circuit protection on all outputs.
Case overload protected @ 110-160% of normal rating
Overvoltage protection 30% to 50% above nominal output
Remote sense
Compensates for 0.5 V lead drop max. Will operate without remote
sense connected. Reverse connection protected.
|
▷ |