English
Language : 

LCC250-12U-4P Datasheet, PDF (1/7 Pages) Artesyn Technologies – 250 Watts Convection/Conduction Mounting
POWER
Data Sheet
LCC250
250 Watts Convection/Conduction Mounting
Total Power: 250 W
# of Outputs: Single
Outputs: 12, 24, 48 V
SPECIAL FEATURES
ƒƒ 250 W full power at elevated
temperatures
ƒƒ Wide operating temperature range
suited for outdoor application
ƒƒ IP64 rated
ƒƒ Conduction-cooled or convection
ƒƒ Differential remote sense
ƒƒ Output adjust
ƒƒ Output On/Off (Positive or Negative
logic user selectable)
COMPLIANCE
ƒƒ EMI Class B
ƒƒ EN61000 Immunity
ƒƒ MIL-STD-461E: CE101; CE102;
CS101; CS114
SAFETY
ƒƒ UL + CSA:
60950-1 2nd Ed.
ANSI ES60601-1
3rd Ed
ƒƒ TUV:
60950-1 2nd Ed.
60601-1 3rd Ed.
61347-1; 2-13
ƒƒ CB Scheme: IEC 60950-1 2nd Ed
IEC 61347-1; 2-13
IEC 60601-1
ƒƒ China
CCC5
ƒƒ CE Mark
Electrical Specifications
Input
Input ra­nge
Frequency
Input fusing
90 - 264 Vac (Operating)
115/230 Vac (Nominal)
47 - 63 Hz
Internal fuse on both L and N lines
Inrush current
50 A
Power factor
Harmonics
> 0.92 Full load
Meets EN61000-3-2; MIL-STD-461E(6); CE101; CE102; CS101; CS104
Input current
Hold up time
Efficiency
Leakage current
3.4 A @ 90 Vac full load
16 ms minimum at 115 Vac; 100% load
230 Vac; 100% load
12 V - 89% typical
24 V - 91% typical
48 V - 91.5% typical
< 275 μA at 230 Vac