DS850DC-3 Datasheet, PDF (1/4 Pages) Artesyn Technologies – Distributed Power Bulk Front-End | |||
|
POWER
Data Sheet
Total Output Power: 650 - 850 Watts
+3.3vdc Stand-by Output
Standard Telco input range -39 V to
-72 VDC
DS650DC-3/DS850DC-3
Distributed Power Bulk Front-End
Special Features
ÂÂ 1U X 2U form factor
ÂÂ 15.4W/ in3
ÂÂ +12Vdc output
ÂÂ +3.3vdc stand-by (5V standby - consult
factory)
ÂÂ No minimum load required
ÂÂ Hot plug operation
ÂÂ N + 1 redundant
ÂÂ Internal ORâing fets
ÂÂ Active current sharing
2PSU shared from 30% to 100%
4PSU shared from 20% to100%
ÂÂ Built-in cooling fan (40mm x 28mm)
ÂÂ I2C communication Interface bus
ÂÂ EEPROM for FRU data
ÂÂ Amber/green bi-color LED status
ÂÂ Internal fan speed control
ÂÂ Fan fail tach output signal
ÂÂ One year warranty
Safety
ÂÂ UL/cUL 60950 (UL recognized)
ÂÂ NEMKO+ CB report EN60950
ÂÂ CE mark
ÂÂ China CCC
DC Input
Connector input shown
Electrical Specifications
Input
Input raÂnge:
-40 Vdc to -75 Vdc
Efficiency:
> 80% typical
Conducted EMI:
FCC Subpart J EN55022 Class B
Radiated EMI:
FCC Subpart J EN55022 Class B
Hold up time:
1 ms @48 Vdc
Output
Main DC voltage:
+12 V @ 70 A; DS850DC
+12 V @ 52.5 A; DS650DC
Stand-By:
+3.3 Vsb @ 6A (5V @ 4A available)
Adjustment range:
Factory Set, no pot adjustments
Regulation:
+12 Vdc; +5%/-5%
+3.3 Vsb; +5%/-5%
Overcurrent:
+12 Vdc; 77A - 105A - DS850DC;
+12 Vdc 57.75 A - 78.75 A; DS650DC
latches off if overcurrent lasts over 1 second, otherwise it is auto
recovery.
+3.3 vsb, 9A max (hiccup mode)
Overvoltage:
Under voltage:
+12 Vdc; 13.2 - 14.4 Vdc
+3.3 Vsb; 3.76 - 4.30 Vdc
+12 Vdc; 9 - 10.8V (latch off)
Turn-on delay:
2 Second max
+12VOutput Rise Time:
10 - 300 mS, Monotonic Rise
|
▷ |