DS2000-3 Datasheet, PDF (1/4 Pages) Emerson Network Power – Active power factor correction | |||
|
POWER
Data Sheet
DS2000-3
2000 Watts 12 V Distributed Power System
Distributed Power Bulk Front-End
Total Output Power: 2000 Watts
+12 Vdc Main Output
+3.3 or +5.0 Vdc Standby Output
Wide Range Input Voltage:
90 - 264 Vac
SPECIAL FEATURES
ÂÂ Active power factor correction
ÂÂ EN61000-3-2 harmonic compliance
ÂÂ Active AC inrush control
ÂÂ 1U X 3U form factor
ÂÂ 26.14 W / in3
ÂÂ +12 Vdc output
ÂÂ +3.3 Vdc or 5.0 V Standby
ÂÂ No minimum load required
ÂÂ Hot plug operation
ÂÂ N + 1 redundant
ÂÂ Internal ORâing fets
ÂÂ Active current sharing
(10 - 100% load)
ÂÂ Built-in cooling fans
(40 mm x 28 mm)
ÂÂ I2C communication interface bus
ÂÂ PMBus compliant
ÂÂ EEPROM for FRU data
ÂÂ Green and Amber LED status
ÂÂ Internal fan speed control
ÂÂ INTEL, SSI Std. logic timing
ÂÂ INTEL, SSI Std. FRU data format
ÂÂ Two year warranty
SAFETY
ÂÂ UL/cUL 60950 (UL Recognized)
ÂÂ NEMKO+ CB Report EN60950
ÂÂ EN60950
ÂÂ CE Mark
ÂÂ China CCC
Electrical Specifications
Input
Input voltage range
90 - 264 Vac (wide range)
90 - 264 1200 W load, nominal 100 Vac
180 - 264 2000 W load, nominal 200 Vac
Frequency
Inrush current
47 - 63 Hz, single phase AC
40 A maximum inrush current
Efficiency
> 89% typical at full load, high line
Conducted EMI
Radiated EMI
FCC Subpart J EN55022 Class B
FCC Subpart J EN55022 Class B
Power factor
0.99 typical
Leakage current
Hold-up time
1.40 mA @ 240 Vac
10 ms minimum
Output
Main DC voltage
+12 V @ 164.2 A 180 - 264 Vac
+12 V @ 100 A 90 - 264 Vac
Standby
+3.3 Vsb @ 9 A or 5 V @ 6 A
Adjustment range
Factory set, no pot adjustments
Regulation
+12 Vdc; ±5%
+3.3 Vsb/+5.0V; ±5%
Overcurrent
+12 Vdc; latches off if overcurrent lasts over 1 second,
otherwise it is auto recovery (See ordering info next page)
Overvoltage
+12 Vdc; 13.2 - 14.4 Vdc
+3.3 Vsb: 3.76 - 4.30 Vdc, +5.0Vsb: 5.5 - 6.25Vdc
Undervoltage
Turn-on delay
+12 Vdc; 9 - 10.8 V (latch off)
2 second max
+12 V output rise time
5 - 300 ms, Monotonic Rise
|
▷ |