English
Language : 

DPF600 Datasheet, PDF (1/2 Pages) Artesyn Technologies – Dual output 600 Watt AC/DC PFC front-end for distributed power architectures
Patent No. 5446366
[ 2 YEAR WARRANTY ]
DPF600 SERIES
Dual output
• 600W front end
• EN61000-3-2 compliant
• Hot pluggable
• N+1 redundancy
• Full set of status signals
• EN55022, EN55011 conducted emissions level B
• UL, TÜV, CSA and BABT approvals
The DPF600 is a 600W universal input AC/DC front end power supply in a fully
enclosed hot pluggable case with built-in fan, front panel with handle, IEC input
connector, on/off switch and DIN output signal connector. Providing dual 49V and 5V
outputs with a full set of status signals, the DPF600 is designed as a slot-in front end
for distributed power systems. The DPF600 provides 600W of output power and is
fully compliant with EN61000-3-2. Standard features include current sharing and full
protection against overvoltage, overload and short circuit. Remote or local system
monitoring is possible via a full set of status signals that include fan fail, DC good,
remote inhibit and current monitoring. The DPF600, with full international safety
approval and the CE mark, meets conducted emissions EN55022 level B. The
DPF600 is designed for use as a front end in medium power communication
applications adopting distributed power architecture. The DPF600 can be used in
conjunction with our complete range of 3 to 200W DC/DC converters to fully configure
a distributed power system.
SPECIFICATION All specifications are typical at nominal input, full load at 25°C unless otherwise stated
OUTPUT SPECIFICATIONS
Voltage set point
-49VDC ±245mVDC
with 2A load applied
Total regulation
Main output
Full load to no load
±5.0%
Rise time
At turn-on
0.5s, max.
Transient response
Main output
50% to 100%
step at 1.0A/µs
5.0% max. dev.,
1ms recovery
to 1.0%
Ripple and noise
(0Hz to 30MHz)
Main output
Auxiliary output
750mV pk-pk,
100mV pk-pk
Overvoltage protection Latching main output
Latching
-55V to -60V
5.7V to 6.5V
Output power limit
750W
Short circuit protection Non-latching
Auto-recovery
Current sharing
±10%, 3V droop from
15% to 100%
INPUT SPECIFICATIONS
Input voltage range
85 to 264VAC
Input frequency range
47Hz to 63Hz
Input surge current
230VAC, cold start @ 25°C 35A max.
Input surge
300VAC
20ms
Safety ground
leakage current
120VAC, 60Hz
230VAC, 50Hz
0.2mA
0.4mA
Input current
90VAC, 600W
220VAC
7.35A rms max.
2.84A rms max.
Input fuse
Non-replaceable
15A
Power factor
0.99 120Vin, >66% load
PAGE 1
EMC CHARACTERISTICS
Radiated emissions EN55022/11, FCC part 15
Conducted emissions EN55022/11, FCC part 15
Harmonic current emm. EN61000-3-2
Electrical fast
transients/bursts
EN61000-4-4
Surge susceptibility EN61000-4-5
Level A
Level B
Compliant
Level 3
Level 3
GENERAL SPECIFICATIONS
Hold-up time
120VAC, 60Hz FL
20ms @ 600W
Efficiency
100Vin, load >66% rated 82% min.
Isolation voltage
Input/output
Input/chassis
3000VAC
1500VAC
Switching frequency
50kHz
Approvals and
standards
EN60950, UL1950, BABT
CSA C22.2 No. 950
Weight
6.9kg (15Ibs)
MTBF
500,000 hours
demonstrated
ENVIRONMENTAL SPECIFICATIONS
Thermal performance
Operating ambient
Non-operating
0°C to +50°C
-40°C to +85°C
50°C to 70°C ambient Derate to 50%
Cooling
Built-in fan
Relative humidity
Non-condensing
5% to 85% RH
Altitude
Operating
Non-operating
10,000 feet max.
40,000 feet max.
Vibration
5Hz to 500Hz
2.4G rms peak
International Safety Standard Approvals
TÜV VDE0805/EN60950/IEC950
UL1950 File No. E136005
CSA C22.2 No. 950 File No. LR41062C
Certificate No. 606090