English
Language : 

MSC60 Datasheet, PDF (2/4 Pages) Arch Electronics Corp. – Switching Power Modules for PCB Mounting
MSC60 SERIES
VER : A_1 update : 2015.03.09
AC-DC Power Module
60 Watts
ELECTRICAL SPECIFICATIONS
All specifications valid at normal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Model No. ( Single Output )
Safety
Approval
Conducted and radiated EMI
MSC60-5S MSC60-9S
MSC60-12S
MSC60-15S
MSC60-24S
cUL/UL 60950-1,
ANSI/AAMI ES 60601-1: 2005, 1st Edition and CAN/CSA-C22.2 No. 60601-1:08, 2nd Edition,
2XMOPP (Pending)
EN55011 (Pending)
ESD
EN61000-4-2 air ± 8kV , Contact ± 4kV Pending
Radiated Immunity
EN61000-4-3 10V/m Pending
Fast Transient
EN61000-4-4 ± 2kV Pending
EMC
Surge
EN61000-4-5 ±1kV Pending
Conducted Immunity
EN61000-4-6 10Vrms Pending
PFMF
EN61000-4-8 30A/m Pending
Dips
EN61000-4-11 30% 10ms Pending
Interruption
EN61000-4-11 >95% 5000ms Pending
NOTE
1. This product is not designed for use in critical life support systems, equipment used in hazardous environment,
nuclear control systems or other such applications which necessitate specific safety and regulatory standards
other the ones listed in this datasheet.
2. Ripple & Noise are measured at 20MHz of bandwidth with 0.1uF & 47uF parallel capacitor.
3. Safety approvals cover frequency 47-63 Hz.
4. That “natural convection” is about 20LFM but is not equal to still air (0 LFM).
5. It's recommended to add Varistor 14S471K at L / N input side in parallel.
6. Please refer to our PDF file "AC-DC Application" on our website: www.archcorp.com.tw
MECHANICAL DIMENSION ( Top View )
PIN#
1
2
3
4
5
6
7
Single
AC IN (L)
AC IN (N)
+DC OUT
NO PIN
-DC OUT
NO PIN
NO CONNECT
http://www.archcorp.com.tw
TEL: +886-2-26989508 FAX: +886-2-26981319
-2-