English
Language : 

A-1966 Datasheet, PDF (2/2 Pages) Amphenol Corporation – HVAC Duct Temperature Sensor
Application Information
A-1996 Dimensions (mm)
Nominal Resistance Ohm
Weight
Operating Temperature
Storage Temperature
Response Time
2.4 grams
-22°F to 185°F (-30°C to 85°C)
-40°F to 194°F (-40°C to 90°C)
< 5 seconds (in oil)
Unloaded Resistance Temperature Table
Temp (°C)
-40
-35
-30
-25
-20
-15
-10
-5
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
Nominal
Resistance
Ohms
100,865
72,437
52,594
38,583
28,582
21,371
16,120
12,261
9,399
7,263
5,658
4,441
3,511
2,795
2,240
1,806
1,465
1,195
980.3
808.8
670.9
559.4
468.7
394.6
333.8
283.5
Resistance
Tolerance
(+/- %)
4.87
4.64
4.43
4.21
4.00
3.80
3.60
3.40
3.21
3.06
2.92
2.78
2.68
2.50
2.45
2.40
2.36
2.31
2.27
2.23
2.19
2.15
2.11
2.07
2.04
2.00
Amphenol
Advanced Sensors
www.amphenol-sensors.com
© 2015 Amphenol Corporation. All Rights Reserved. Specifications are subject to change without notice.
Other company names and product names used in this document are the registered trademarks or
trademarks of their respective owners.
AAS-920-667A - 12/2015