TR-11CX630.5A Datasheet, PDF (1/3 Pages) Altech corporation – UL1077 Recognized Supplementary Protector/ Circuit Breaker for Equipment
TR11 Series
E209569
up to 12 Amps
UL1077 Recognized
Supplementary Protector/
Circuit Breaker for Equipment
Applications:
Protection of single phase Motors, Transformers,
UPS, Power strips, Solenoids etc., against
damage due to overcurrent conditions.
Current Rating
Rated Voltage
Initial insulation resistance
Dielectric strength
Overload Switching Capacity
Maximum Breaking Capacity
Power Loss
Operating Temperature
Operational Life at 2xIn
Limited short circuit current
Terminals
Applicable Standards
Approvals
Accessories
0.5 -16.0A
240V AC, 50/60Hz, 32V DC / 24V DC (VDE)
> 100 M ohms.
(As per EN 60934)
1.5 KV for One minute.
(As per EN 60934)
6 In ~ up to 9.0A
4 In - up to 12.0A
(As per EN 60934)
60A Max. ~ from 10.0A to 12.0A
60A Max. - from 10.0A to 12.0A
8x In for <6.0A
60A MAX. for > 6.0A
1 - 2 Watts
Maximum 60°C Ambient
1000 Cycles
1000 Amps PC 1
0.25” Quick connect
EN 60934, CSA 22.2 No. 235, UL-1077
up to 16.0 A
upto 12.0A
Dust Cover, DC-TR11 C (see page 14)
Time Current Characteristics:
The standard characteristic is valid for ambient temperatures of
+23°C. If the device is to be used in an ambient temperature other
than +23°C, allowances must be made when selecting the current
rating according to the following guidelines:
Ambient temp. °C
Correction Factor
-20 -5 0 +10 +20 +30 +40 +50 +60
0.8 0.88 0.9 0.96 1 1.05 1.12 1.2 1.3
Example :
Normal Continuous Current
Ambient Temperature
Correction Factor
Recommended Current Rating
Select the nearest
: 1.8A
: 40°C
: 1.12
: 1.8 x 1.12 = 2.016
: 2.0A
Operating
Characteristic
(min) 60
30
20
10
5
1
(S) 50
20
10
5
2
1
0.5
0.2
0.1
1.05 1.32 2
3 45
Multiple of Rated Current
8 10
Rated current
Ambient
Temperature
<6A
>6A
23°C