2C03UM Datasheet, PDF (1/2 Pages) Altech corporation – V-EA-Series - UL508 Manual Motor Controller
V-EA-Series - UL508 Manual Motor Controller - 2 pole C-Trip
UL508 Listed
E137938
Two Pole
Standard Pack: 6
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
35 mm
(1.38 in.)
74.7 mm
(2.94 in.)
93.3 mm
(3.67 in.)
35 mm
(1.38 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
2C03UM
2C05UM
2C075UM
NA
2C1UM
2C1.6UM
2C2UM
2C2.5UM
2C3UM
2C3.5UM
2C4UM
2C5UM
2C6UM
2C8UM
2C10UM
NA
2C13UM
2C15UM
2C16UM
2C20UM
2C25UM
2C30UM
2C32UM
2C40UM
2C50UM
2C60UM
2C63UM
Approvals
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
Amp Range
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
all
0.3 - 10A
all
12 - 30/32A
all
40 - 50A
all
60 / 63A
*up to nearest rated current
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
10kA
5kA
5kA
5kA
V-EA-C Trip
0.3A Through 10A Rated Current
1.13-1.45xIN
60
40
10
Thermal Overload
4
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 20 40
100
Multiple of Rated Current
V-EA-C Trip
13A Through 63A Rated Current
1.13-1.45xIN
60
40
10
Thermal Overload
4
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 20 40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Ring
tongue
Box
clamp