English
Language : 

1G03UM Datasheet, PDF (1/2 Pages) Altech corporation – V-EA-Series - UL508 Manual Motor Controller -
V-EA-Series - UL508 Manual Motor Controller - 1 pole G-Trip
UL508 Listed
E137938
One Pole
Standard Pack: 12
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
74.7 mm
(2.94 in.)
17.5 mm
(0.69 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1G03UM
1G05UM
NA
1G08UM
1G1UM
1G1.6UM
1G2UM
1G2.5UM
1G3UM
1G3.5UM
1G4UM
1G5UM
1G6UM
1G8UM
1G10UM
1G12UM
1G13UM
1G15UM
1G16UM
1G20UM
1G25UM
1G30UM
1G32UM
1G40UM
1G50UM
1G60UM
1G63UM
Approvals
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
277VAC
0.3-25A: 1 pole - 42VDC
30-60A: 1 pole - 24VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
Amp Range
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
all
0.3 - 10A
all
12 - 30/32A
all
40 - 50A
all
60 / 63A
*up to nearest rated current
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
10kA
5kA
5kA
5kA
V-EA-G Trip
0.3A Through 10A Rated Current
1.05-1.35xIN
60
40
10
Thermal Overload
4
“Must Trip” = 125% Rated Current
“Must Not Trip” < 1 hr = 135% RC
1
“Must Not Trip” > 1 hr = 105% RC
“Must Not Trip” = Rated Current
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 20 40
100
Multiple of Rated Current
V-EA-G Trip
12A Through 63A Rated Current
1.05-1.35xIN
60
40
10
Thermal Overload
4
“Must Trip” = 125% Rated Current
“Must Not Trip” < 1 hr = 135% RC
1
“Must Not Trip” > 1 hr = 105% RC
“Must Not Trip” = Rated Current
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 20 40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Ring
tongue
Box