English
Language : 

1E03UM Datasheet, PDF (1/2 Pages) Altech corporation – V-EA-Series - UL508 Manual Motor Controller
V-EA-Series - UL508 Manual Motor Controller - 1 pole E-Trip
UL508 Listed
E137938
One Pole
Standard Pack: 12
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
74.7 mm
(2.94 in.)
17.5 mm
(0.69 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1E03UM
1E05UM
1E075UM
NA
1E1UM
1E1.6UM
1E2UM
1E2.5UM
1E3UM
1E3.5UM
1E4UM
1E5UM
1E6UM
1E8UM
1E10UM
1E12UM
1E13UM
1E15UM
1E16UM
1E20UM
1E25UM
1E30UM
1E32UM
1E40UM
1E50UM
1E60UM
1E63UM
Approvals
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
277VAC
0.3-25A: 1 pole - 42VDC
30-60A: 1 pole - 24VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
Amp Range
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
UL-Listed
MCCB
up to 10kA
No BCP
Required
up to:
all
0.3 - 10A
all
12 - 30/32A
all
40 - 50A
all
60 / 63A
*up to nearest rated current
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
10kA
5kA
5kA
5kA
V-EA-E Trip
0.3A Through 10A Rated Current
1.05-1.35xIN
60
40
10
4
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 1418 20 40
100
Multiple of Rated Current
E0.3A-E10A
V-EA-E Trip
12A Through 60A Rated Current
1.05-1.35xIN
60
40
10
4
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 14 18 20 40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Ring
tongue
Box
clamp