English
Language : 

1DU05R Datasheet, PDF (1/2 Pages) Altech corporation – R-Series - UL1077 Supplementary Protecto
R-Series - UL1077 Supplementary Protecto - 1 pole D-Trip
E301611
One Pole
Standard Pack: 12
Weight:
0.5A - 63A: 1.6kg (3.54 lb.)
Rated
Current
0.5A
1.0A
2.0A
3.0A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1DU05R
1DU1R
1DU2R
1DU3R
1DU4R
1DU5R
1DU6R
1DU8R
1DU10R
1DU12R
1DU13R
1DU15R
1DU16R
1DU20R
1DU25R
1DU30R
1DU32R
1DU40R
1DU50R
1DU60R
1DU63R
45 (1.77 in.)
6.5 (0.26 in.)
44 (1.73 in.)
60 (2.36 in.)
77 (3.03 in.)
17.5 (0.69 in.)
Voltage Rating
Short Circuit Withstand Rating
(UL - Ratings)
Interrupting Capacity
(IEC/EN60898/60947-2)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability:
Solid Wire
Stranded Wire
Terminal Torque
Terminal Protection Degree
Vibration Resistance
277VAC
0.5-6A (RC): 10kA with no back-up fuse
8-63A (RC): 10kA with UL-listed
Class J back-up fuse; 5kA with no back-up fuse
0.5-63A (RC): 10kA
30°C (86°F)
-25° to 60°C (-13° to 140°F)
-25° to 75°C (-13° to 167°F)
18 AWG -10 AWG
18 AWG -3 AWG (Line/Load reversible)
2.8 Nm (25 lb-in.)
IP20
3g (18-50Hz)
B, C and D Trip, Less than 10A
120
60
40
20
10
68
4
2
1
40
20
10
5
1
0.5
0.1
0.05
0.01
1
BC D
2
3 4 5 6 7 8 9 10 12 14 16 20
1.13 1.45
Multiple of Rated Current
B, C and D Trip, 10A and higher
7200
3600
2400
1200
600
480
360
240
120
60
40
20
10
5
1
0.5
0.1
0.05
0.01
1
1.13 1.45
BC D
2
3 4 5 6 7 8 9 10 12 14 16 20
Multiple of Rated Current
short circuit WithstAND rAtiNgs for
r-series supplemeNtAry protector
Backup Protection
Trip Amp
Curve Range
UL-Listed No Backup Fuse
Class J Fuse
Required
up to 10kA
up to:
All 0.5 - 6A
4xRC*
10kA
All 8 - 63A
4xRC*
5kA
*up to nearest rated current