1C03UM Datasheet, PDF (1/2 Pages) Altech corporation – V-EA-Series - UL508 Manual Motor Controller
V-EA-Series - UL508 Manual Motor Controller - 1 pole C-Trip
UL508 Listed
E137938
One Pole
Standard Pack: 12
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
74.7 mm
(2.94 in.)
17.5 mm
(0.69 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
60A
63A
Type/
Cat. No.
1C03UM
1C05UM
1C075UM
NA
1C1UM
1C1.6UM
1C2UM
1C2.5UM
1C3UM
1C3.5UM
1C4UM
1C5UM
1C6UM
1C8UM
1C10UM
NA
1C13UM
1C15UM
1C16UM
1C20UM
1C25UM
1C30UM
1C32UM
1C40UM
1C50UM
1C60UM
1C63UM
Approvals
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
277VAC
0.3-25A: 1 pole - 42VDC
30-60A: 1 pole - 24VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
short circuit Withstand ratings for v-ea manual motor controller
V-EA-C Trip
0.3A Through 10A Rated Current
1.13-1.45xIN
60
40
10
Thermal Overload
4
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 20 40
100
Multiple of Rated Current
V-EA-C Trip
13A Through 63A Rated Current
1.13-1.45xIN
60
40
10
Thermal Overload
4
“Must Trip” < 1 hr = 145% RC
“Must Not Trip” > 1 hr = 113% RC
1
10
4
1
0.4
10-1
4x10-2
10-2
4x10-3
10-3
1
2 3 4 5 6 8 10 20 40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
Trip
Curve
Amp Range
Backup
Protection
UL-Listed
RK5-Fuse
up to 10kA
all
0.3 - 10A
all
12 - 30/32A
all
40 - 50A
all
60 / 63A
*up to nearest rated current
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
UL-Listed
MCCB
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
No BCP
Required
up to:
10kA
5kA
5kA
5kA
Ring
tongue
Box