English
Language : 

80024 Datasheet, PDF (1/2 Pages) Alpha Wire – 7 Components Cabled
Part Number: 80024
Page 1 of 2 Pages
A. Construction
1) Component 1
a) Conductor
b) Insulation
(1) Print
(2) Color Code
ALPHA WIRE
CUSTOMER PRODUCT SPECIFICATION
Issue:
Issue Date:
Effective Date:
1
3/24/2015
5/19/2015
Diameters (In)
7 X 1 COND
20 (26/34) AWG Tinned Copper
0.035
0.010" Wall, Nom. MPPE
0.055
ALPHANUMERIC NUMBERS - 1-ONE ALTERNATING AND
INVERTED
Alpha Wire Color Code KX
Cond
1
2
3
Color
GREEN/YELLOW
BLACK#1
BLACK#2
Cond
4
5
6
Color
BLACK#3
BLACK#4
BLACK#5
Cond
7
Color
BLACK#6
2) Cable Assembly
7 Components Cabled
a) Twists:
6.0 Twists/foot (min)
b) Core Wrap
Nonwoven Polyester Tape, 25% Overlap, Min.
3) Jacket
0.032" Wall, Nom.,Polyurethane, Zero Halogen (ZH)
0.234+/- 0.012
a) Color(s)
SLATE
b) Print
ALPHA WIRE-* P/N 80024 7C 20 AWG
RU AWM STYLE 21959 90C 600V SUN RES 60C OIL OR
CRU AWM I/II A/B 90C 600V FT2 --- IEC EN 60332-1/2
CE ROHS (SEQ FOOTAGE)
* = Factory Code
B. Applicable Specifications
1) UL
a) Component 1
AWM/STYLE 11231
105°C / 600 VRMS
b) Overall
AWM/STYLE 21959
60C OIL
90°C / 600 VRMS
SUN RES
2) CSA International
C(RU) AWM I/II A/B
FT2
90°C / 600 VRMS
3) IEC
a) Component 1
EN 60228 Conductors, Class 6
b) Overall
EN 60754-1 Acid Gas Generation
EN 60754-2 Acid Gas Generation
EN 60332-1 Flame Behavior
EN 60332-2 Flame Behavior
4) CE:
EU Low Voltage Directive 2006/95/EC
C. Environmental Compliance
1) CE:
EU Directive 2011/65/EU(RoHS2):
This product complies with European Directive 2011/65/EU (RoHS Directive) of the
European Parliament and of the Council of 8 June 2011. No Exemptions are
required for RoHS Compliance on this item. Consult Alpha Wire's web site
for RoHS C of C.
2) REACH Regulation (EC 1907/2006):
This product does not contain Substances of Very High Concern (SVHC) listed on
the European Union's REACH candidate list in excess of 0.1% mass of the item. For
up-to-date information, please see Alpha's REACH SVHC Declaration.
D. Physical & Mechanical Properties
1) Temperature Range
-50 to 90°C(static), -40 to 80°C (dynamic)
2) Bend Radius
4X Cable Diameter(static), 6X Cable Diameter(dynamic)
3) Pull Tension
57 Lbs, Maximum
4) Sunlight Resistance
Yes
E. Electrical Properties
(For Engineering purposes only)
1) Voltage Rating
600 VRMS
Although Alpha Wire Company ("Alpha") makes every reasonable effort to ensure their accuracy at the time of publication, information and specifications
described herein are subject to errors or omissions and to changes without notice, and the listing of such information and specifications does not ensure
product availability.
Alpha provides the information and specifications herein on an "AS IS" basis, with no representations or warranties, whether express, statutory or implied. In
no event will Alpha be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary) whatsoever, even if Alpha has
been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the
use, or inability to use, the information or specifications described herein.
711 Lidgerwood Ave Elizabeth, NJ 07207-0711
Toll Free 1-800-52 ALPHA • T: 1-908-925-8000 • F: 908-925-5411 • Email: info@alphawire.com
www.alphawire.com