Specifications
Cat. No.
700-SE_ _ _Z05
700-SE_ _ _Z12
700-SE_ _ _Z24
Rated
Control
Voltage
5V DC
12V DC
24V DC
Operating Control
Voltage Range
4…6V DC
9.6…14.4V DC
19.2…28.8V DC
Cat. No.
Rated Load Voltage
700-SE05…
700-SE10…
700-SE20…
100…240V AC
Item
Load Switching Method/Device
Pick-up time
Drop-out time
Output ON voltage drop
Output Leakage current
Output VDRM VCEO (V)
Output di/dt (A/uS)
Output dv/dt (V/uS)
Output I2t (A2S)
Output Tj (°C) max.
Insulation resistance
Dielectric strength
Vibration resistance (max.)
Shock resistance (max.)
Ambient temperature
Ambient humidity
Standards
Weight
Operating
Control/Input Ratings ➊
Input Impedance
Control Voltage Levels
With Zero
Cross Function
Without Zero
Cross
Function
Pick-up Voltage
Drop-out Voltage
250 Ω ± 20%
300 Ω ± 20%
4V DC max.
600 Ω ± 20%
800 Ω ± 20%
9.6V DC max.
1V DC min.
1.6k Ω ± 20%
19.2V DC max.
Load/Output Ratings
Applicable Load
Load Voltage Range
Continuous Load Current (Resistive)
With Heat Sink ➋
Without Heat Sink ➋
Min.
Max.
Min.
Max.
Max. Inrush Current
➌
0.1 A
5A
0.1 A
5A
60 A (@50/60 Hz,
1 cycle)
75…264V AC
0.1 A
10 A
0.1 A
5A
150 A (@50/60 Hz,
1 cycle)
0.1 A
20 A
0.1 A
5A
220 A (@50/60 Hz,
1 cycle)
Characteristics
700-SE_ _ _Z…
700-SE_ _ _N…
Triac
1/2 of load power source cycle + 1 ms max.
1 ms max.
1/2 of load power source cycle + 1 ms max.
1.6 V (RMS) max.
5 mA max. (at 100V AC)
10 mA max. (at 200V AC)
600
600
SE05GZ=100
SE10GZ & SE20 GZ =50
SE05GN=100
SE10 GN & SE20GN =50
SE05GZ=200, SE10GZ=500, SE20GZ=100
SE05GN =200, SE10GN =500, SE20GN
=100
SE05GZ =24.5, SE10GZ =60, SE20GZ =260
SE05GN =24.5, SE10GN =60, SE20GN =260
125
125
100 MΩ min. (at 500V DC)
2,000V AC, 50/60 Hz for 1 min.
10…55 Hz, 1.5 mm double amplitude (10 G)
1,000 m/s2 (100 G)
Operating: –30…80°C (–22…176°F) with no icing or condensation
Storage: –30…100°C (–22…212°F) with no icing or condensation
45…85% (no condensation)
UL 508, CSA C22.2 , TUV, CE
Approx. 37 g
➊ Each 5 A, 10 A, and 20 A model has 5V DC, 12V DC, and 24V DC input versions.
➋ Refer to "Load Current Vs. Ambient Temperature Characteristics" graphs page 45 regarding maximum load current with and without heat sinks.
➌ If the SSR operation is continuous ON/OFF, this value should be reduced by 50%. Refer to the “Inrush Current Resistivity” graphs on page 45 for more details.
44