English
Language : 

MSR238 Datasheet, PDF (1/2 Pages) Allen-Bradley – Modular Monitoring Safety Relays
Safety Relays
Modular Monitoring Safety Relays
Minotaur MSR238
Description
The MSR238 is an time-delayed output expansion module for the
modular Minotaur MSR200 family of monitoring safety relays. It can
be connected to either the MSR210 or MSR211 base unit or to the
MSR230output module to provide time-delayed outputs.
Up to 2 output modules can be connected to one base unit by simply
removing the terminator, included with each base unit, and
connecting the ribbon cables of the neighboring module. The
connecting ribbon cable provides power to the MSR238 as well as a
check on its status. The terminators must be inserted into the final
output module.
The MSR238 has two safety rated outputs that work in parallel with
the safety outputs of the base unit. When the output of the base unit
is activated, the outputs of the MSR238 are the user-selected time
delay expires. The time delay is set by connecting jumpers to the
wiring terminals.
The outputs are 2 normally open safety rated outputs. The safety
outputs have independent and redundant internal contacts to help
ensure the safety function. The delayed normally closed output is an
auxiliary signal that must only be used to indicate the status of the
MSR238.
Features
• Category 3 per EN 954-1
• Stop category 1
• 2 Diagnostic LEDs
• Removable terminals
• 2 N.O. Delayed Safety Outputs
• 1 N.C. Delayed Aux. Output
Specifications
Standards
EN 954-1, ISO 13849-1, IEC/EN
60204-1, IEC 60947-4-1, IEC
60947-5-1, ANSI B11.19, AS4024.1
Approvals
C-Tick, CE marked for all
applicable directives, cULus and
TUV
Category
Cat. 3 per EN954-1 (ISO13849-1)
Power Supply
24V DC from the base unit
Power Consumption
2.5W
Fuses
Output (Ext. Recommended) 6A Slow Blow or 10A Quick Blow
Outputs
2 N.O. Safety
1 N.C. Auxiliary
Output Utilization per IEC
60947-4-1 (Resistive)
AC-1: 6A/250V AC
DC-1: 6A/24V DC
➊ Output Utilization per IEC
60947-5-1 (Inductive)
B300, AC-15
3A/250V AC, 3A/125VAC
P300, DC-13
2.5A/24V DC
Thermal Current (non switching) 1x6A, 2x4A
Min. Switched Current/Voltage 10mA/10V DC
Contact Material
AgSnO2 with 2 micron gold plating
Indication LEDs
Green = CH1 Output Active
Green = CH2 Output Active
Impulse Withstand Voltage
2500V
Pollution Degree
2
Operating Temperature
-5°C to +55°C (+23°F to 141°F)
Humidity
95% RH
Enclosure Protection
IP40 (NEMA 1)
Terminal Protection
IP20
Maximum Conductor Size
0.2 – 2.5mm2 (24-12 AWG)
Torque Settings—term. screws 0.4 – 0.5 Nm (3.54 – 4.43 lb²in)
Case Material
Polyamide PA 6.6
Mounting
35mm DIN rail
Weight
215 (0.47lbs)
Electrical Life
222V AC/4A/880VA cosϕ=0.35
220V AC/1.7A/375VA cosϕ=0.6
30V DC/2A/60W
10V DC/0.01A/0.1W
100,000 operations
500,000 operations
1,000,000 operations
2,000,000 operations
Mechanical Life
10,000,000 cycles
Vibration
10-55 Hz, 0.35mm
Shock
10g, 16ms, 100 shocks
➊ See Output Ratings on page 1-29 for details. Consult factory for ratings not
shown.
4-82