English
Language : 

MSR15D Datasheet, PDF (1/2 Pages) Allen-Bradley – Monitoring Safety Relays with Delayed Outputs
Safety Relays
Monitoring Safety Relays with Delayed Outputs
Minotaur MSR15D
Specifications
Description
The MSR15D has 2 N.C. dual channel input for use with gate
interlocks and emergency stop buttons in higher risk applications.
The MSR15D has output monitoring that can accommodate an
automatic/manual reset. Automatic/manual reset can use a jumper
or can be used to check operation of the contacts.
The MSR15D has 3 N.O. safety outputs, 1 N.C. auxiliary output and
1 N.O. delayed safety output. The delay is set by an internal
potentiometer. The safety outputs have independent and redundant
internal contacts to help ensure the safety function. The auxiliary
contact is a nonsafety output intended to provide an external signal
about the status of the safety outputs.
Features
• Safety category 3
• Stop category 0 and 1
• 2 N.C. dual channel input
• 2 N.O. safety outputs
• 1 N.O. safety delayed output
• 1 N.C. auxiliary output
• Automatic/manual reset
• 45mm wide housing
The safety function is ensured by the Minotaur
Standards
EN 954-1, ISO13849-1, IEC/EN
60204-1, IEC 60947-5-1, ANSI
B11.19, AS4024.1
Category
Cat. 3 per EN 954-1 (ISO 13849-1)
Approvals
C-Tick, CE marked for all
applicable directives, cULus & TÜV
Power Supply
24V AC/DC
Power Consumption
<4VA
Safety Inputs
2 N.C.
Input Simultaneity
0.5s
Maximum Input Resistance
500 Ω
Reset
Automatic/Manual
Outputs
➊ Output Utilization per IEC
60947-5-1 (Inductive)
2 N.O. Safety; 1 N.C. Auxiliary
B300, AC-15
4A/250V AC, 4A/125V AC
P300, DC-13; 2A/24V DC
Thermal Current (non switching) 4A
Fuses Input (internal, replace.) 500mA time lag
Output (external)
5A quick acting
Min. Switched Current/Voltage 10mA/10V
Maximum Dropout Time
90ms
Indication LEDs
Red = Power On
Green = K1 Closed
Green = K2 Closed
Impulse Withstand Voltage
2500V
Installation Group
C in accordance with VDE 0110
Pollution Degree
3
Operating Temperature
-10°C to +55°C (+14°F to +131°F)
Humidity
90% RH
Enclosure Protection
IP40, (NEMA 1), DIN 0470
Terminal Protection
IP20, DIN 0470
Conductor Size
1 x 2.5mm2 (14AWG) stranded,
1 x 4mm2 (12AWG) solid
Torque Settings—terminal
screws
1N⋅m (8.85lb⋅in)
Case Material
Red Polycarbonate
Mounting
35mm DIN rail
Weight
230g (.51lbs)
Electrical Life
220V AC/4A/880VA cosϕ=0.35
220V AC/1.7A/375VA cosϕ=0.6
30V DC/2A/60W
10V DC/0.01A/0.1W
100,000 operations
500,000 operations
1,000,000 operations
2,000,000 operations
Mechanical Life
2,000,000 operations
Vibration
0.75mm (0.30in) peak, 10-55Hz
Shock
30g, 11ms half sine
➊ See Output Ratings on page 1-29 for details. Consult factory for ratings not
shown.
Switch circuit MSR15D
monitors for any single
fault that may cause a
danger.
MSR15D
monitors itself
for any internal
fault.
Contactors:
Provides contactor
monitoring if two or
more contactors are
used in series.
4-44