English
Language : 

800EP-MTS44 Datasheet, PDF (1/7 Pages) Allen-Bradley – Push Buttons
Emergency Stop Devices
Push Buttons
800 E-Stops !
Specifications—22.5mm
Front of Panel (Operators)
Mechanical Ratings
Description
Plastic
(800EP/ES)
Metal
(800EM/EB)
Vibration (assembled to
panel)
Shock
Degree of protection
Mechanical design life
(typical)
Environmental
Temperature range
(operating): per IEC 947-1
Temperature range (short
term storage): per IEC
947-1
Materials
Bushings, mounting rings
Bezels
Seals: diaphragm style
Seals: lip and flat gasket
styles
Illuminated lenses
10 to 2000Hz, 1.52mm displacement
(peak-to-peak) max./10g max.
1/2 cycle sine wave for 11ms and no
damage at 100g
IP66 (NEMA Type 3, IP66 (NEMA Type 3,
3R, 4, 4X, 12, 13) 3R, 4, 12, 13)
500,000 cycles:
mushroom
100,000 cycles:
operators
mushroom key
operators (plastic),
push-pull/twist
50,000 cycles:
operators
mushroom key
operators (metal)
-25°C to +55°C (-13°F to +131°F) ➋
-40°C to +70°C (85°C max. for 24 hours)
-40°F to +158°F (185°F max. for 24 hours)
Glass-filled
thermoplastic
polyester, rated
UL94 V-O
Glass-filled
thermoplastic
polyester, rated
UL94 V-O
Silicone rubber
Nitrile rubber
Die-cast zinc; dark
olive chromate
finish
Anodized aluminum
(EB, EM, ES line)
Transparent nylon Type 12
! See Performance Data: refer to page Important-2 of the A113 Industrial Controls
catalogue.
➋ Operating temperature below 0°C (32°F) are based on the absence of freezing
moisture and liquids.
➌ Per IEC 947-1.
➍ UL File & Guide Number E14840.
Back of Panel Components
Electrical Ratings
Description
2-Across Style 3-Across Style
Standard contact block
ratings➋
Thermal current
Terminal marking
Wire capacity (screw
terminal)
Dielectric strength (min)
Electrical design life cycles
Electrical shock
protection: Per IEC 529
Mechanical Ratings
NEMA, EEMAC
NEMA, A600,
A600, Q600, VDE Q600, 600V AC;
0660; AC15, DC 13 AC15, DC 13 to
to IEC 947
IEC 947
10A max.
10A max. without
continuous current enclosure (40°C
to UL508, CSA22.2 (104°F) ambient) 6A
#14, IEC 947, VDE with enclosure
0660, part 200
(60°C (140°F))
Conforming to CENELEC EN50013
Min of (1) #20AWG #18 to #12AWG
Max of (2)
#14AWG or (1)
#12AWG
(0.75 to 2.5mm2)
Max (2) #14AWG
or (1) #12 AWG
2,200V for one minute
1,000,000 at 2A
Finger-safe conforming to IP2X
Vibration
Shock
Contact block mechanical
design
Contact operation
Operating forces (typical)
Environmental
10 to 2000Hz
1.52mm
displacement (peak-
to-peak) max./10g
max. 6hr
1/2 cycle sine wave
for 11ms and no
damage at 100g min
5,000,000 cycles
10 to 150Hz
0.15mm
displacement (peak-
to-peak) max./2g
max. 6hr
1/2 cycle sine wave
for 11ms and no
damage at 50g max
N.C. slow make, double break (positive
opening); N.C.L.B. late break, double
break (positive opening)
2.78N: all contact 2.6N: each N.C.
blocks
contact block
Temperature range
Operating ➋➌
Short term storage ➌
Materials
-25°C to +55°C (-13°F to +131°F)
-25°C to +55°C (70°C max for 24 hrs)
(-13°F to +131°F (158°F max for 24 hrs))
Springs
Stainless steel and zinc coated music wire
Electrical contacts:
Standard
Silver nickel alloy Fine silver
Low voltage
Palladium silver
Gold-plated over
alloy: spanner; gold- silver
plated silver nickel:
stationary contacts
Terminals: Screw type Plated steel
Push-on type
Agency approvals
Approvals
UL listed ➍/CSA certified
Standard conformity
UL508, UL486E
NEMA ICS-1 and
CSA22.2 #14,
ICS-2 IEC 204-1,
NEMA ICS-1 and 947; SEV 1005,
ICS-2 (1983), IEC 1093; VDE 0113,
144, IEC 947-1, IEC 0660 Part 201; BS
947-5, VDE 0550, 4794; CEE 24; UL
VDE 0660, Part 200 486E, UL 508,
CSA22.2 #14
6-14