Features
• Mechanically linked contacts meeting IEC 947-5-1-L
• 2…12 poles – all mechanically linked
• Red faceplate for easy identification of safety circuits
• IEC mechanically linked contacts symbol displayed on front
• Double-break contacts to reduce probability of welded contacts
• Visual indication of contact state
• Tamper resistant cover helps prevent changes which could
jeopardize safety
• Complete Catalogue number displayed on front
• Ideal for use in safety circuits
Specifications
Contactors & Control Relays
Safety Control Relays
700S-P
Type
700S-P
Contact Rating Continuous
10 A @ 600V AC / 5 A @ 600V DC
Ratings
AC
Make/Break
DC
NEMA A600
NEMA P600
Min. Contact Switching Ratings
10V, 50 mA
Contacts
in Series
Volts DC
24 64 125 250 500 600
1
DC Switching
2
5A 2.2A 1.1A 0.55A 0.24A 0.2A
10A 10A 5A 2A 0.7A 0.5A
3
— — 7A 3A 1.5A 1.0A
4
— — 10A 5A 2.5A 1.5A
Contact Electrical Life—
Resistive Loads
1.5 mil. ops. at 10A break at 120V AC
14 mil. ops. at 1A break at 120V AC
6 mil. ops. at 1A break at 24V DC
Coil Voltage
Range ➊
AC
DC
Battery
Charging
85…110%
80…110%
85…115%
50 Hz
60 Hz
Coil
AC
Con-
sump-tion
DC
Inrush
Sealed
Inrush
Sealed
132 VA
19.3 VA
138 VA
19 VA
12.7 W
12.7 W
Mechanically Linked
Contacts
All contacts are mechanically linked
per IEC 947-5-1 annex L for 2 to 12
poles
Operating
Time
Mechanical Life
Pick-up
Dropout
AC – 10…20 ms / DC – 30…50 ms
AC – 10…20 ms / DC – 20…33 ms
12.5 million operations ➋
Contact Arrangement
2 to 12 Poles, Double Break Contacts
N.O. or N.C. (8 N.C. Maximum)
Contact Material/Design
Silver Nickel/Bifurcated
Mounting
Panel mount or mount on 700-MP Rail
Horizontal Mounting Recommended
Temperature
Operating➌
Storage
–20…+65°C (–4…149°F)
–40…+65°C (–40…149°F)
Wire size per UL/CSA
1X #18 AWG…2X #12 AWG
Tightening Torque
8…12 lb-in. (0.9…1.4 N•m)
➊ Coil voltage required for proper operation (percent of rated coil voltage).
➋ 90% of devices are expected to meet or exceed 12.5 million operations,
and 50% of devices are are expected to meet 20 million operations.
➌ Temperature inside the panel.