English
Language : 

440T-MSRUE11 Datasheet, PDF (1/2 Pages) Allen-Bradley – Solenoid Release Units
Prosafe Trapped Key Interlock Switches
Solenoid Release Units
Description
The solenoid release unit is used for electrical isolation of machinery
to enable safe access. It consists of a rotary power switch (RPS) and
a solenoid. The trapped key can be removed once an external signal
is given to its internal solenoid locking mechanism. An indicator
light on the SRU indicates when trapped key can be removed; that is,
when power is applied to the solenoid. The solenoid signal only
needs to be present when key removal is necessary. The solenoid is
rated for 100% duty cycle. Power to the solenoid can be removed
after the trapped key is removed.
Removing the trapped key causes the isolating power switch to
change state; the normally open contacts open and the normally
closed contacts (if applicable) will close.
The trapped key can then be used in the next sequence of the
operation.
Features
• Direct drive operation—positively opens contacts
• Integral solenoid monitoring
• Key trapped until release signal is applied
• IP 65 enclosure or panel mounted versions
• LED or NEON “key free” indication
• 316L stainless steel construction
• 24V DC, 110V AC/DC or 230V AC solenoid options
• Weatherproof stainless steel dust cap as standard
• UL and CSA approval on switches
• Single or multiple key units available (contact factory)
• Replaceable code barrel assembly
Specifications
Standards
EN292-1&2, EN1954-1, IEC/EN60204-1,
EN1088, IEC/EN60947-5-1, ISO13849-
1, ISO12100-1&2, ISO14119, GS-ET-19,
AS4024.1
Category
Cat. 1 per EN 954-1 (ISO 13849-1)
Suitable for Cat. 2, 3, and 4 systems
Approvals
BG, cULus and CE marked for all
applicable directives
Solenoid Voltage
24V DC, 110V AC, 230V AC, 110V DC
Solenoid Power
DC Types 6.5W continuous
AC Types 6VA continuous
Electrical Characteristics
See rotary power switches
Mounting
Any position
Max Shear Force to Key
15.1kN (3398lbs)
Max Torque to Key
14Nm (124lb•in)
Material
Trapped Key Components 316L Stainless Steel
Face Plate 316L Stainless Steel
Optional Box ABS Plastic
Cable
0.75sq. mm2 (18AWG) 2-wire PVC
jacket QD
Operating Temperature
0°C to +40°C (+32°F to +104°F)
Humidity
95% RH
Environmental
With Optional Plastic IP65 (NEMA 13)
Enclosure
Electrical Life
>100,000
Mechanical Life
100,000
The Prosafe Advantage
5-12
Stainless steel
construction.