Isolation Specifications
Parameters
Tested I/O voltage
Isolation resistance
Conditions
60 sec
Series AMES15-MAZ
15 Watt | AC-DC / DC-DC Converter
Typical
>1000
Rated
4000
Units
VAC
MΩ
General Specifications
Parameters
Switching frequency
Protection class
Start up time
Over load protection
Over voltage protection
Short circuit protection
Case material
Operating temperature
Storage temperature
Max Case temperature
Temperature coefficient
Cooling
Humidity
Weight
Dimensions (L x W x H)
MTBF
Conditions
Typical
Maximum
132
Class II
350
Foldback
>130
Zener diode clamp
Auto recovery
Metal
With derating over 55 oC (10CFM)
-40 to +80
-50 to +100
100
±0.02
Free air convection
95
100
3.62 x 2.56 x 0.94 inches 92.0 x 65.0 x 24.0 mm
> 400,000hrs (MIL-HDBK -217F, t=+25oC)
> 100,000hrs (MIL-HDBK -217F, t=at highest operating temperature)
Units
KHz
mS
%
oC
oC
oC
% / oC
% RH
g
NOTE: All specifications in this datasheet are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at
rated output load unless otherwise specified.
Environment Approval
Parameters
Wave form: Half sine wave
Conditions
Acceleration amplitude: 5gn
Shock
Bump duration: 30 ms
Number of bumps: 18 (3 in each direction for every axis)
Converter operation before and after test, body mounted (on chassis)
Test mode: Sweep sine
10-100Hz, speed 0.05Hz/s
Vibrations
Displacement: 1mm
Acceleration: 3g
3 loops 30min one cycle, 3h total, every axis tested
Converter operation before and after test, body mounted (on chassis)
Safety & EMC Specifications
Parameters
Agency approvals
cULus, CE, CB
Medical Electrical Equipment
IEC\EN\UL 60601-1, 2 x MOOP, CSA-C22.2 No.
601.1-M90
Information technology Equipment
EN 60950-1:2006+A11:2009
EMI - Conducted and radiated emission
EN55011, class B
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage fluctuations and flicker
IEC/EN 61000-3-3, (EN60555-3)
Standards
Electrostatic Discharge Immunity
RF, Electromagnetic Field Immunity
IEC 61000-4-2 Level 3
IEC 61000-4-3 Level 2
Electrical Fast Transient/Burst Immunity
IEC 61000-4-4 Level 3
Surge Immunity
IEC 61000-4-5 Level 3
RF, Conducted Disturbance Immunity
IEC 61000-4-6 Level 2
Power frequency Magnetic Field Immunity
IEC 61000-4-8 Level 2
Voltage dips, Short Interruptions Immunity
IEC 61000-4-11
www.aimtec.com
F 052e R7.R
Tel: +1 514 620 2722
2 of 5
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only