English
Language : 

AM150HB-UZ Datasheet, PDF (1/4 Pages) AIMTEC – 150 Watt | Half Brick DC-DC Converter
FEATURES:
• RoHS compliant
• Wide 2:1 Input range
• Very low ripple and noise
• On/Off Control and Trim Function
Series AM150HB-UZ
150 Watt | Half Brick DC-DC Converter
• Regulated output
• High efficiency
• Operating temperature range: -40 to +85ºC
• 1500VDC I/O Isolation
Models
Single output
Model
AM150HB-2403S-UZ
AM150HB-2405S-UZ
AM150HB-2412S-UZ
AM150HB-2415S-UZ
AM150HB-2424S-UZ
AM150HB-2428S-UZ
AM150HB-2448S-UZ
AM150HB-4803S-UZ
AM150HB-4805S-UZ
AM150HB-4812S-UZ
AM150HB-4815S-UZ
AM150HB-4824S-UZ
AM150HB-4828S-UZ
AM150HB-4848S-UZ
AM150HB-11005S-UZ
AM150HB-11012S-UZ
AM150HB-11015S-UZ
AM150HB-11024S-UZ
Input Voltage (V)
18-36
18-36
18-36
18-36
18-36
18-36
18-36
36-72
36-72
36-72
36-72
36-72
36-72
36-72
66-160
66-160
66-160
66-160
Output Voltage
(V)
3.3
5
12
15
24
28
48
3.3
5
12
15
24
28
48
5
12
15
24
Output Current max (A)
30
30
12.5
10
6.3
5.4
3.1
30
30
12.5
10
6.3
5.4
3.1
30
12.5
10
6.3
Input Filter
π type
π type
L type
L type
L type
L type
L type
π type
π type
L type
L type
L type
L type
L type
π type
L type
L type
L type
NOTE: All specifications are measured at an ambient temperature of 25°C, humidity<75%, nominal input voltage and at rated
output load unless otherwise specified.
Input Specifications
Parameters
Voltage range
Remote Control
Logic Low
Turn On Time
Start-up Delay Time
Nominal
24
48
110
CNTRL open or connect to +Vin
CNTRL connect to –Vin
Typical
18-36
36-72
66-160
On
Off
10
150
Maximum
0.4
Units
VDC
V
ms
ms
Isolation Specifications
Parameters
Tested I/O voltage
Tested Input / Case voltage
Tested Output / Case voltage
Conditions
1 Min
1 Min
1 Min
Typical
1500
500
500
Maximum
Units
VDC
VDC
VDC
Output Specifications
Parameters
Set point accuracy
Trim range
Dynamic Response
Short Circuit protection
Short Circuit restart
www.aimtec.com
F 054e R3.F
Conditions
200µs setting time
Typical
±1
±10
50-75% & 50-25% load
Continuous
Auto recovery
Tel: +1 514 620 2722
1 of 4
Maximum
3% of Vout
Units
%
%
Pk deviation
Toll free: + 1 888 9 AIMTEC
(924 6832)
North America only