English
Language : 

30C50 Datasheet, PDF (1/3 Pages) American Electronic Components, inc – Industry Standard Mounting
30C50
definite purpose contactor
• 30C 50FLA Definite Purpose Contactor
• Robust 2 & 3 Pole Contactor
• Arc Covers as standard
• Industry Standard Mounting
• RoHS Compliant
• UL File No: E61703
Contact Data
Arrangements:
Material:
2 Form X (2PST-NO-DM)
3 Form X (3PST-NO-DM)
AgCdO, AgSnOInO
Table 1
Model No
Full Load
Amps (FLA)
Poles
Line Voltage Locked Rotor
(VAC)
Amps (LRA)
Resistive
Amps
120
300
30C50-1022
50
240/277
300
2
65
480
250
600
200
120
300
30C50-1023
50
240/277
300
3
65
480
250
600
200
FLA rating tested for 6000 cycles of endurance at 240/480/600VAC per UL508.
Resistive Heat rating tested for 250,000 cycles at 277VAC.
LRA rating tested for 6000 cycles of Locked Rotor endurance per UL508.
Voltage
120
240
120
240
480
600
Max. HP
1 Phase
3
10
3
10
3 Phase
15
15
25
25
Coil Data
Voltage: 24-277VAC 50/60Hz. See coil data below. (480VAC available but not UL approved)
Insulation Class: UL Class B (130°C)
Coil
Voltage
Code
Rated
Voltage
50/60Hz
Coil
Resistance
(Ohms)
Coil Operating Voltage (VAC)
Must
Release
Must
Operate
Max
Voltage
Minimum Inrush
VA @ 50Hz VA @ 60Hz
Table 2
Nominal Coil Power
VA @ 50Hz VA @ 60Hz
5024
24
2.4
6
18
30
138
130
18
13
5120
120
45
20
88
132
138
130
18
13
5230
208/240
180
40
177
264
138
130
18
13
5277
277
280
65
220
300
138
130
18
13
5480
480
852
150
384
520
138
130
18
13
Page 1 of 3
www.aecsensors.com
Ref: 30C50 101711JHM
Sales Department Tel: (888) 847-6552