Features
 Unique IO design for local & remote IO
 Universal input supports 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA, RTD, Thermistor
(3K, 10K), and digital input (Dry contact)
 Analog output supports 0 ~ 10 V, 0 ~ 20 mA, and 4 ~ 20 mA (BAS-3024 only)
 Supports PWM output (BAS-3024 only)
BAS-3018
BAS-3024
RoHS
COMPLIANT
2002/95/EC
Introduction
BAS-3018/BAS-3024 expansion I/O modules can be stacked on the DDC controller, or can serve as remote standalone I/O modules through an RS-485 network. These expansion I/O
modules add both scalability and flexibility to Advantech BAS-3000 solutions. Like the DDC, I/O expansion modules can be programmed using the BASPro programming tool.
Specifications
General
 Power Input
 Power Consumption
24 VDC/24 VAC
3 W @ 24 VDC (BAS-3018)/4 W @ 24 VDC (BAS-3024)
Universal Input
 Channels
8 (BAS-3018)/4 (BAS-3024)
 Resolution
16-bit
 Sample Rate
10 Hz (Total)
 Accuracy
±0.1% of FSR (Voltage, Current)
 Type and Range
Analog Input: 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA,
Pt-100/1000, RTD, Thermistor (3 k, 10 k)
Digital Input Logic High: Close
(Dry Contact) Logic Low: Open
 Over Voltage Protection ±35 V
Analog Output (BAS-3024 only)
 Channels
 Resolution
 Accuracy
4
12-bit
± 0.1% of FSR
 Range
0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA
Digital Output (BAS-3024 only)
 Channels
4 (Source Type)
 Vcc
10 ~ 35 VDC, Current: 1 A (per channel)
 PWM output (2 channels)
Minimum Period
1 second (for PWM output)
Minimum Pulse Width 0.1 second (for PWM output)
Protection
 Isolation Voltage
3,000 VDC
Ordering Information
 BAS-3018-AE
 BAS-3024-AE
8-ch UI Expansion Module
4-ch UI, 4-ch AO, 4-ch DO Expansion Module
Common Specifications
General
 Dimension (W x H x D) 120 x 120 x 44 mm
 Enclosure
ABS + PC
 Watchdog Timer
Yes
 Operating Mode
 Communication
1. Connect to BAS-3520/3512
(Powered by BAS-3520/3512)
2. Standalone as remote I/O devices
(Need external power 24 VDC)
Local Bus (Connect to BAS-3520/3512)
RS-485 (Standalone as remote I/O devices)
Environment
 Operating Temperature -10 ~ 60° C
 Storage Temperature
 Operating Humidity
 Storage Humidity
-20 ~ 80° C
20 ~ 95% (Non-condensing)
0 ~ 95% (Non-condensing)
Online Download www.advantech.com/products